Power System Frequency Measurement Under Nonstationary Situations

A new method for the measurement of the instantaneous power-system frequency is proposed. It is based on the frequency estimation of the voltage signal using three equidistant samples. An algorithm is developed that diminishes the variance of the estimation. The procedure is applied to the case of single- and three-phase networks, and uncertainty in the frequency estimation is obtained with simulated signal and severe conditions of signal quality. A frequency variation has been assumed as plusmn2 Hz around the nominal value, with a maximum rate of change of 1 Hz/s. The uncertainty of 25 mHz and 3.5 mHz has been obtained for single- and three-phase signals, respectively. A low-cost virtual instrument has been developed to make frequency measurements over the actual voltage signal.

[1]  R. Micheletti,et al.  REAL-TIME MEASUREMENT OF POWER SYSTEM FREQUENCY , 2000 .

[2]  Udaya Annakkage,et al.  A comparison of frequency measurement methods for underfrequency load shedding , 1998 .

[3]  Milos Sedlacek,et al.  Low uncertainty power-line frequency estimation for distorted and noisy harmonic signals , 2004 .

[4]  Boualem Boashash,et al.  Estimating and interpreting the instantaneous frequency of a signal. II. A/lgorithms and applications , 1992, Proc. IEEE.

[5]  G. Bucci,et al.  On-line digital measurement for the quality analysis of power systems under non-sinusoidal conditions , 1996, Quality Measurement: The Indispensable Bridge between Theory and Reality (No Measurements? No Science! Joint Conference - 1996: IEEE Instrumentation and Measurement Technology Conference and IMEKO Tec.

[6]  T. Inoue,et al.  Estimation of power system inertia constant and capacity of spinning-reserve support generators using measured frequency transients , 1997 .

[7]  H. Wayne Beaty,et al.  Electrical Power Systems Quality , 1995 .

[8]  G. Andria,et al.  Windows and interpolation algorithms to improve electrical measurement accuracy , 1989 .

[9]  A. T. Johns,et al.  Frequency relaying based on instantaneous frequency measurement [power systems] , 1996 .

[10]  Milos Sedlacek,et al.  Interpolations in frequency and time domains used in FFT spectrum analysis , 1998 .

[11]  V. Eckhardt,et al.  Dynamic measuring of frequency and frequency oscillations in multiphase power systems , 1989 .

[12]  Giovanni Bucci,et al.  On-line digital measurement for the quality analysis of power systems under nonsinusoidal conditions , 1999, IEEE Trans. Instrum. Meas..

[13]  M.J. Devaney,et al.  A new quadratic form based frequency measurement algorithm , 1996, Quality Measurement: The Indispensable Bridge between Theory and Reality (No Measurements? No Science! Joint Conference - 1996: IEEE Instrumentation and Measurement Technology Conference and IMEKO Tec.

[14]  Ronald M. Adelson Frequency Estimation from Few Measurements , 1997, Digit. Signal Process..