An experimental exergetic comparison of four different heat pump systems working at same conditions: As air to air, air to water, water to water and water to air

In this study, we designed a multifunctional heat pump system using just one scroll compressor and which can be run in four different modes, namely air to air, air to water, water to water and water to air, in order to make an experimental energetic and exergetic performance comparison. Experimental system consists of two condensers and two evaporators and uses R22 as working fluid. One of the evaporators and condensers uses water and the others use air as heat source/sink. Heating capacities of four heat pump types are equal to each other. It is realized by adjusting the mass flow rate and temperature level of external fluid of condenser. Results show that the heat pump unit which has the maximum COP (coefficient of performance) value is water to air type with 3.94 and followed by water to water type with 3.73, air to air type with 3.54 and air to water type with 3.40. Ranking of four heat pump types with respect to their mean exergy efficiency is as follows; water to air type with 30.23%, air to air type with 30.22%, air to water type with 24.77% and water to water type with 24.01%. Exergy destruction rates of the systems were investigated in this study and the results revealed that the heat pump type which has the maximum exergy destruction is air to air type with 2.93 kW. The second highest one is air to water type with 2.84 kW. The third highest one is water to air type with 2.64 kW and last one is water to water type with 2.55 kW. It is understood that the temperature of the evaporator external fluid affects the exergetic efficiency of the system more than the mass flow rate. In contrast to the previous, the dominant parameter which has more important effect on the exergy destruction of the heat pump unit is the mass flow rate of evaporator external fluid.

[1]  Ibrahim Dincer,et al.  Exergy: Energy, Environment and Sustainable Development , 2007 .

[2]  S. P. Lohani Energy and exergy analysis of fossil plant and heat pump building heating system at two different dead-state temperatures , 2010 .

[3]  Omer Comakli,et al.  Determination of optimum working conditions R22 and R404A refrigerant mixtures in heat-pumps using Taguchi method , 2009 .

[4]  O. Comakli,et al.  Energy analysis of a solar-ground source heat pump system with vertical closed-loop for heating appl , 2011 .

[5]  Bertha Maya Sopha,et al.  Norwegian households' perception of wood pellet stove compared to air-to-air heat pump and electric heating , 2010 .

[6]  Gerry Carrington,et al.  Exergy analysis of an isothermal heat pump dryer , 2011 .

[7]  O. Büyükalaca,et al.  Experimental investigation of Seyhan River and dam lake as heat source–sink for a heat pump , 2003 .

[8]  Mehmet Kaya,et al.  The relation of collector and storage tank size in solar heating systems , 2012 .

[9]  Philippe Goffin,et al.  Low exergy building systems implementation , 2012 .

[10]  Onder Ozgener,et al.  A parametrical study on the energetic and exergetic assessment of a solar-assisted vertical ground-source heat pump system used for heating a greenhouse , 2007 .

[11]  Jiangfeng Guo,et al.  The application of entransy theory in optimization design of Isopropanol–Acetone–Hydrogen chemical heat pump , 2012 .

[12]  Uğur Çakır,et al.  The role of cogeneration systems in sustainability of energy , 2012 .

[13]  Arif Hepbasli,et al.  A comparative study on exergetic assessment of two ground-source (geothermal) heat pump systems for residential applications , 2007 .

[14]  Josua P. Meyer,et al.  A techno-economic analytical comparison of the performance of air-source and horizontal-ground-source air-conditioners in South Africa , 1997 .

[15]  M. Picon Nunez,et al.  Exergy analysis and optimization of a solar-assisted heat pump , 1998 .

[16]  J. Urchueguía,et al.  Comparison between the energy performance of a ground coupled water to water heat pump system and an air to water heat pump system for heating and cooling in typical conditions of the European Mediterranean coast , 2008 .

[17]  S. J. Kline,et al.  Describing Uncertainties in Single-Sample Experiments , 1953 .

[18]  Ibrahim Dincer,et al.  Effect of varying dead-state properties on energy and exergy analyses of thermal systems , 2004 .

[19]  D. Jung,et al.  Thermodynamic performance of R32/R152a mixture for water source heat pumps , 2012 .

[20]  Ruzhu Wang,et al.  Experimental performance analysis and optimization of a direct expansion solar-assisted heat pump water heater , 2007 .

[21]  Ji Jie,et al.  Comparative study of air-source heat pump water heater systems using the instantaneous heating and cyclic heating modes , 2011 .

[22]  Mustafa Inalli,et al.  A techno-economic comparison of ground-coupled and air-coupled heat pump system for space cooling , 2007 .

[23]  Guoqiang Zhang,et al.  The performance of an open-loop lake water heat pump system in south China , 2006 .