Evaluation of breakdown characteristics of CO2 gas for non-standard lightning impulse waveforms - breakdown characteristics for double-frequency oscillation waveforms under non-uniform electric field

Since SF6 gas, an insulation medium used for gas insulated switchgear (GIS), has a high global warming potential, an effective alternative is sought from an environmental perspective. The authors are focusing on CO2 gas as a potential alternative, given its relatively good insulation characteristics among gases with a low environmental impact (natural gases). The present study obtained and evaluated the insulation characteristics for complex waveforms, such as double-frequency oscillation waveforms, generated in an actual substation under a non-uniform electric field typically represented by metallic particle. Consequently, it was emerged that the breakdown voltage for a positive polarity waveform was 1.1 to 1.6 times higher than that for the standard lightning impulse waveform; even if parameters such as the frequency and damping rate were changed within the range assumed in the field. Furthermore, a study was conducted on a means of evaluating the insulation characteristics of the CO2 gas gap for non-standard lightning impulse waveforms via an approach involving comprehensive handling of various waveforms, as was applied to the experimental results accumulated to date. Consequently, using a parameter of so-called duration, the breakdown characteristics for various waveforms, including complex oscillation waveforms generated in actual systems, could be expressed using a single characteristic line.

[1]  James K. Olthoff,et al.  Sulfur hexafluoride and the electric power industry , 1997 .

[2]  L. B. Wagenaar,et al.  VOLTAGE-TIME CHARACTERISTICS OF BREAKDOWN IN SF6 , 2013 .

[3]  Hisashi Goshima,et al.  Lightning Impulse Breakdown Characteristics of High-Pressure N2 as an Alternative Insulation Gas to SF6 , 2001 .

[4]  S. Okabe,et al.  Evaluation of breakdown characteristics of CO2 gas for non-standard lightning impulse waveforms - breakdown characteristics in the presence of bias voltages under non-uniform electric field , 2013, IEEE Transactions on Dielectrics and Electrical Insulation.

[5]  S. Okabe,et al.  Evaluation of breakdown characteristics of gas insulated switchgears for non-standard lightning impulse waveforms - breakdown characteristics in the presence of bias voltages under non-uniform electric field , 2009, IEEE Transactions on Dielectrics and Electrical Insulation.

[6]  S. Okabe,et al.  Evaluation of breakdown characteristics of CO2 gas for non-standard lightning impulse waveforms - breakdown characteristics under double-frequency oscillation waveforms and single-frequency oscillation waveforms in the presence of bias voltage , 2012, IEEE Transactions on Dielectrics and Electrical Insulation.

[7]  M. Hikita,et al.  Fundamental insulation characteristics of high-pressure CO2 gas for gas-insulated power equipment - effect of coating conductor on insulation performance and effect of decomposition products on creeping insulation of spacer - , 2008, IEEE Transactions on Dielectrics and Electrical Insulation.

[8]  S. Okabe,et al.  Evaluation of breakdown characteristics of gas insulated switchgears for non-standard lightning impulse waveforms - method for converting non-standard lightning impulse waveforms into standard lightning impulse waveforms - , 2009, IEEE Transactions on Dielectrics and Electrical Insulation.