Six-pulse converter atypical harmonics caused by second harmonic voltage
暂无分享,去创建一个
This paper reports the orders and levels of atypical harmonics caused by the second harmonic voltage. Two basic types of 6-pulse converters are discussed: The L-filter (current source rectifier) and the C-filter (voltage source rectifier). The response of these converters to symmetrical nonsinusoidal voltage distorted by positive- and negative-sequence 2nd harmonic voltage are summarized. The most significant finding reported in this study is the fact that C-filter converters supplied with traces of positive-sequence 2nd harmonic voltage are prone to inject excessive amount of dc and even harmonic currents into the ac lines.
[1] A. E. Hammad,et al. Analysis of second harmonic instability for the Chateauguay HVDC/SVC scheme , 1992 .
[2] John A. Orr,et al. On the need for strict second harmonic limits , 2000 .