Analysis on Current Limiting and Recovery Characteristics of a SFCL using a Trigger of Superconducting Element

As one of the countermeasures to improve the recovery characteristics of the SFCL (superconducting fault current limiter), the method using the trigger of high-TC superconducting element (HTSC) when the quench in the HTSC element occurred was proposed. To confirm the suggested method, the control circuit to detect the quench occurrence of HTSC element in case of the fault occurrence was designed and the current limiting and recovery experiments of the SFCL using the designed control circuit were performed. Through the analysis for the experimental results, the points of both the open time and the closing time of a power switch comprising the control circuit could be adjusted by the resistance amplitude of a normal conducting current limiting resistor (CLR) and the recovery characteristics of the SFCL together with the current limiting operation could be confirmed to be improved by using the control circuit.