Effects of Environmental Factors on Partial Discharge Activity and Estimation of Insulation Lifetime in Electrical Machines

Partial discharges (PD) are produced in the stator insulation of electrical machines while energized. The sources of PD are internal voids, crack, and manufacturing defects, which keep on extending with its normal operation, leading to the complete failure of insulation. The intensity of PD is considerably influenced by the environmental factors, including surrounding temperature, pressure, humidity, and contamination. This paper investigates the influence of these factors on the PD activity in electrical machines and estimates the lifetime of insulation. The PD measurements were conducted by placing the motors in a climate-controlled chamber. The PD trend under varying environmental stresses was investigated over time. Accordingly, PD inception voltage and various discharge characteristic parameters such as accumulated apparent charge, cumulative energy function, average discharge current, discharge power, and quadratic rate have been determined. The combined effect of various environmental stresses on the PD activity was also investigated. The mathematical relationships were developed to estimate the discharge characteristics as the functions of pressure and temperature using the Gaussian model and the Exponential model. Finally, the endurance of insulation was estimated under different environmental conditions based on the average discharge current to differentiate between correct and incorrect PD measurements and to develop a right maintenance schedule for motors in service.

[1]  Greg C. Stone,et al.  Experience With Online Partial-Discharge Measurement in High-Voltage Inverter-Fed Motors , 2016, IEEE Transactions on Industry Applications.

[2]  J. van Duivenbode,et al.  Operational conditions influencing the partial discharge performance of cables under low and medium vacuum , 2019, IEEE Transactions on Dielectrics and Electrical Insulation.

[3]  J. Kuffel,et al.  High Voltage Engineering: Fundamentals , 1984 .

[4]  Pietro Romano,et al.  On PD mechanisms at high temperature in voids included in an epoxy resin , 2001 .

[5]  Alun S. Vaughan,et al.  The effect of voltage, temperature and morphology on electrical treeing in polyethylene blends , 2000 .

[6]  Thierry Lebey,et al.  Development of a new off-line test procedure for low voltage rotating machines fed by adjustable speed drives (ASD) , 2003 .

[7]  Andre Agneray,et al.  Pressure effects on the development of an electric discharge in non-uniform fields , 2001 .

[8]  M.D. Judd,et al.  Partial discharge monitoring of power transformers using UHF sensors. Part I: sensors and signal interpretation , 2005, IEEE Electrical Insulation Magazine.

[9]  G. Stone,et al.  Investigations into the effect of humidity on stator winding partial discharges , 2005, IEEE Transactions on Dielectrics and Electrical Insulation.

[10]  Jacob Cohen,et al.  Applied multiple regression/correlation analysis for the behavioral sciences , 1979 .

[11]  Ghulam Murtaza Hashmi,et al.  Partial discharge detection for condition monitoring of covered-conductor overhead distribution networks using Rogowski coil , 2008 .

[12]  Ian Cotton,et al.  The effects of pressure and temperature on partial discharge degradation of silicone conformai coatings , 2017, IEEE Transactions on Dielectrics and Electrical Insulation.

[13]  P.H.F. Morshuis,et al.  Assessment of dielectric degradation by ultrawide-band PD detection , 1995 .

[14]  B. T. Phung,et al.  Partial discharge localization in transformers using UHF detection method , 2012, IEEE Transactions on Dielectrics and Electrical Insulation.

[15]  G.C. Stone,et al.  Application of Partial Discharge Testing to Hydro Generator Maintenance , 1984, IEEE Transactions on Power Apparatus and Systems.

[16]  Matti Lehtonen,et al.  The Smart Solution for the Prediction of Slowly Developing Electrical Faults in MV Switchgear Using Partial Discharge Measurements , 2013, IEEE Transactions on Power Delivery.

[17]  W. G. Chadband Electrical Degradation and Breakdown in Polymers , 1992 .

[18]  Ian Cotton,et al.  Impact of low pressure aerospace environment on machine winding insulation , 2010, 2010 IEEE International Symposium on Electrical Insulation.

[19]  R. Khazaka,et al.  Polyimide lifetime under partial discharge aging: effects of temperature, pressure and humidity , 2013, IEEE Transactions on Dielectrics and Electrical Insulation.

[20]  O. M. Nassar,et al.  Motor Insulation Degradation Due to Switching Surges and Surge Protection Requirements , 1986, IEEE Transactions on Energy Conversion.

[21]  K. Younsi,et al.  Seasonal changes in partial discharge activity on hydraulic generators , 2001, Proceedings: Electrical Insulation Conference and Electrical Manufacturing and Coil Winding Conference (Cat. No.01CH37264).

[22]  Jose L. Torero,et al.  SFPE handbook of fire protection engineering , 2016 .

[23]  Jiancheng Song,et al.  Influences of humidity and temperature on oil contamination discharge of HV motor stator windings , 2016, IEEE Transactions on Dielectrics and Electrical Insulation.

[24]  T. W. Dakin,et al.  Measurement of Corona Discharge Behavior at Low Pressure and Vacuum , 1967 .

[25]  K. Younsi,et al.  Stator winding failures: contamination, surface discharge, tracking , 1999, Industry Applications Society 46th Annual Petroleum and Chemical Technical Conference (Cat.No. 99CH37000).

[26]  A. H. Bonnett,et al.  Analysis of the impact of pulse-width modulated inverter voltage waveforms on AC induction motors , 1994, Proceedings of IEEE Pulp and Paper Industry Conference.

[27]  Ghulam Amjad Hussain,et al.  Methods for Arc-Flash Prediction in Medium Voltage and Low Voltage Switchgear , 2015 .

[28]  Muhammad Shafiq,et al.  Design and Implementation of Partial Discharge Measurement Sensors for On-line Condition Assessment of Power Distribution System Components , 2014 .

[29]  G.C. Stone,et al.  Effect of manufacturer, winding age and insulation type on stator winding partial discharge levels , 2004, IEEE Electrical Insulation Magazine.

[30]  T. Lebey,et al.  Existence of partial discharges in low-voltage induction machines supplied by PWM drives , 1996 .

[31]  R. Bartnikas,et al.  Surface conductivity of epoxy specimens subjected to partial discharges , 1990, IEEE International Symposium on Electrical Insulation.