Lightning flashover rates of overhead distribution lines applying volt time curve from testing and IEEE Std.1410-2004
暂无分享,去创建一个
This paper calculates the lightning flashover rates of 22 kV overhead distribution line. In order to calculate the backflashover rate (BFOR), the performance of line which related to the insulator backflashover has been modeled and analyzed using Electromagnetic Transient Program (EMTP). The shielding failure flashover rate (SFFOR) and induced voltage flashover rate (IVFOR) have been calculated follow equations given in IEEE std 1410-2004. Finally the total numbers of flashovers of line have been determined. The lightning flashovers rates of BFOR, SFFOR and IVFOR have also been compared with the data taken from the line outages recorder. From the system being studied shown that, the total numbers of flashovers from simulation and calculation is closed to the data from the line outage recorder.
[1] T. Hara,et al. Modelling of a transmission tower for lightning-surge analysis , 1996 .
[2] T. Thanasaksiri. Lightning performance of covered conductors overhead distribution lines , 2010, ECTI-CON2010: The 2010 ECTI International Confernce on Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology.
[3] H. Elahi,et al. Modeling guidelines for fast front transients , 1996 .