A system for the measurement of the loss tangent and capacitance of high-voltage insulation over a wide range of frequency and voltage

There is no need to determine the high-voltage characteristics of high-voltage insulation systems used in high-powered electrical machines in order to evaluate the relevance of 0.1 Hz measurements to those taken at power frequency and to investigate their value for diagnostic purposes. A computer-controlled system for the generation of test voltages and the measurement of loss tangent and capacitance in the range 1 mHz to 1 kHz and 100 V to 22 kV RMS is described. The high voltage generator is basically a class B amplifier with an output rating of 30 kV (peak) and 100 mA (peak). The measurement system is based on the analysis of the out-of-balance signal of a modified capacitance bridge. The accuracy of the system is discussed and measurements from samples of high-voltage conductor bar insulation used in turbo-generators are presented.

[1]  A. K. Jonscher,et al.  The ‘universal’ dielectric response , 1977, Nature.

[2]  B. V. Bhimani,et al.  Very-Low-Frequency High-Potential Testing , 1961, Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems.

[3]  D. Ellison,et al.  A high-voltage test generator for insulation testing , 1983 .

[4]  R. Miller,et al.  Partial Discharge Measurements over the Frequency Range 0.1 Hz to 50 Hz , 1977, IEEE Transactions on Electrical Insulation.

[5]  R. Miller,et al.  A variable low frequency high voltage generator using valves with fibre optic light guide control , 1975 .