Tolerance analysis of flicker Pst short term perceptibility assessment for one minute observation time

This paper present the tolerance analysis and evaluation of flicker severity Pst short term perceptibility assessment for 1 minute observation time based on IEC61000-4-15 flickermeter standard. The evaluation approach takes a complete range of standard rectangular modulated test waveform set for evaluation of both 10 minutes and the 1 minute observation time. The tolerance is then derived from the error evaluated from Pst of 1 and 10 minutes observation time. The proposed 20% tolerance is then verified with actual recorded waveform from the field. The result shows that the proposed tolerance is generally valid for 1 minute Pst assessment with one conditional limitation. The proposed tolerance serves as a supplementary guide for 1 minute Pst assessment to compliment the 10 minutes Pst assessment.

[1]  Giovanni Bucci,et al.  The Performance Evaluation of IEC Flicker Meters in Realistic Conditions , 2008, IEEE Transactions on Instrumentation and Measurement.

[2]  Carmine Landi,et al.  Design and Calibration of an Objective Flickermeter , 2006, IEEE Transactions on Instrumentation and Measurement.

[3]  Ciro Spataro,et al.  A virtual instrument for measurement of flicker , 1998, IMTC/98 Conference Proceedings. IEEE Instrumentation and Measurement Technology Conference. Where Instrumentation is Going (Cat. No.98CH36222).

[4]  Unai Irusta,et al.  A Precise Analysis of the IEC Flickermeter When Subject to Rectangular Voltage Fluctuations , 2009, IEEE Transactions on Instrumentation and Measurement.

[5]  J. C. Gomez,et al.  Flicker Measurement and Light Effect , 2002, IEEE Power Engineering Review.

[6]  J. Ruiz,et al.  Singular Frequencies in Rectangular Fluctuations in the IEC Flickermeter , 2007, IEEE Transactions on Power Delivery.

[7]  Z. Hanzelka,et al.  Comparative tests of flickermeters , 2002, 10th International Conference on Harmonics and Quality of Power. Proceedings (Cat. No.02EX630).

[8]  Subhashish Bhattacharya,et al.  A Discrete Matlab–Simulink Flickermeter Model for Power Quality Studies , 2010, IEEE Transactions on Instrumentation and Measurement.

[9]  Shyh-Jier Huang,et al.  Enhancement of digital equivalent voltage flicker measurement via continuous wavelet transform , 2004, IEEE Transactions on Power Delivery.

[10]  J. Julio Gutiérrez,et al.  A Review of Flicker Severity Assessment by the IEC Flickermeter , 2010, IEEE Transactions on Instrumentation and Measurement.

[11]  X. Yang,et al.  Power System Flicker Analysis and Numeric Flicker Meter Emulation , 2007, 2007 IEEE Lausanne Power Tech.