A theoretical model to predict frosting limits in cross-flow air-to-air flat plate heat/energy exchangers

Abstract In cold climates, the water vapor in the warm and moist exhaust air may condense and form frost on the heat/energy exchangers’ plate. In this study, a simplified theoretical model to predict the inlet conditions under which frost will form in the flat plate heat/energy exchangers is developed. The model uses the exchanger design parameters and operating conditions to determine the frosting limit. Experimental tests are conducted to validate the frosting limits model. The results show that the predicted frosting limits have consistent agreements with experiments, and energy exchangers have a lower risk of frosting than the heat exchangers. Furthermore, a parametric analysis using the theoretical model is performed to estimate the impacts of number of heat and moisture transfer units (NTUh and NTUm), aspect ratio of aluminum spacer, air flow rate, and membrane permeability on frosting limits of heat/energy exchangers. It is found that air flow rate has significant impacts on frosting limits. The combinations of sensible and latent effectiveness ensuring no frost inside energy exchanger are studied theoretically. The model can be applied to improve the design of exchangers to reduce or avoid frosting for cold climates. The frosting limits of cross-flow membrane energy exchanger can also be regarded as criteria to conduct selection and feasibility analysis of energy exchanger and compare with counter-flow exchanger as a reference in future study.

[1]  Li-Zhi Zhang,et al.  Heat and mass transfer in plate-fin sinusoidal passages with vapor-permeable wall materials , 2008 .

[2]  Carey J. Simonson,et al.  A review of frosting in air-to-air energy exchangers , 2014 .

[3]  Carey J. Simonson,et al.  Material properties and measurements for semi-permeable membranes used in energy exchangers , 2014 .

[4]  J. Niu,et al.  Membrane-based Enthalpy Exchanger: material considerations and clarification of moisture resistance , 2001 .

[5]  G. R. Guinn,et al.  Evaluation of seasonal performance and utility impacts of water spray augmentation of air-cooled condensers , 1985 .

[6]  Miklos Kassai,et al.  Evaluation of defrosting methods for air-to-air heat/energy exchangers on energy consumption of ventilation , 2015 .

[7]  Roy B. Holmberg Prediction of condensation and frosting limits in rotary wheels for heat recovery in buildings , 1989 .

[8]  E. G. Phillips,et al.  Comparison of freezing control strategies for residential air-to-air heat recovery ventilators , 1989 .

[9]  Roy B. Holmberg Sensible and Latent Heat Transfer in Cross-Counterflow Gas-To-Gas Heat Exchangers , 1989 .

[10]  D. R. Fisher,et al.  A model to compare freezing control strategies for residential air-to-air heat recovery ventilators , 1989 .

[11]  Refrigerating ASHRAE handbook of fundamentals , 1967 .

[12]  Alan S. Fung,et al.  Experimental study and analysis of an energy recovery ventilator and the impacts of defrost cycle , 2015 .

[13]  A. London,et al.  Compact heat exchangers , 1960 .

[14]  Hans Martin Mathisen,et al.  Review of heat/energy recovery exchangers for use in ZEBs in cold climate countries , 2015 .

[15]  D. R. Fisher,et al.  Freeze-control strategy and air-to-air energy recovery performance , 1992 .

[16]  Jose Iragorry,et al.  Review Article: A Critical Review of Properties and Models for Frost Formation Analysis , 2004 .