High efficiency H2O/LiBr double effect absorption cycles with multi-heat sources for tri-generation application

The objective of this study is to develop a high-efficiency double effect absorption cycle using multi-heat sources for tri-generation (trigen) application. The trigen system produces electricity, heating and cooling loads at the same time. The double-effect absorption refrigeration system consists of two generators, condensers, solution heat exchangers, expansion valves, an absorber and an evaporator. The cycle simulation is carried out for the H2O/LiBr double effect absorption cycle with multi-heat sources for parallel, serial, reverse, revised serial and revised reverse flow patterns. The absorption refrigeration system uses the high temperature steam and hot water as the multi-heat sources. A new high-efficiency cycle is selected depending on the arrangements of additional heat exchangers. This study recommends HX 2-2 cycle with two additional heat exchangers (SDHHX and DHX) as the best candidate for trigen application. It is concluded that THotwater has much more significant effect on the COP and QE than Tsteam in the HX 2-2 cycle. It is also found that the most important UA to affect the COP is UALG while that to affect QE is UAA.

[1]  M. P. Maiya,et al.  Equilibrium low pressure generator temperatures for double-effect series flow absorption refrigeration systems , 2000 .

[2]  Jason Wonchala,et al.  Solution procedure and performance evaluation for a water–LiBr absorption refrigeration machine , 2014 .

[3]  Yiping Dai,et al.  Parametric analysis for a new combined power and ejector–absorption refrigeration cycle , 2009 .

[4]  Pedro J. Mago,et al.  Combined cooling, heating and power: A review of performance improvement and optimization , 2014 .

[5]  A. Pitale,et al.  A Review on Working Pair Used in Adsorption Cooling System , 2015 .

[6]  M. P. Maiya,et al.  Performance comparison of double-effect parallel-flow and series flow water–lithium bromide absorption systems , 2001 .

[7]  Zeyu Li,et al.  Appropriate heat load ratio of generator for different types of air cooled lithium bromide–water double effect absorption chiller , 2015 .

[8]  Guangming Chen,et al.  A novel absorption refrigeration cycle. , 2010 .

[9]  Omar Abdelaziz,et al.  State-of-the-art review on crystallization control technologies for water/LiBr absorption heat pumps , 2011 .

[10]  Kamaruzzaman Sopian,et al.  Performance enhancement of ejector–absorption cooling cycle by re-arrangement of solution streamlines and adding RHE , 2015 .

[11]  Reinhard Radermacher,et al.  Absorption chiller crystallization control strategies for integrated cooling heating and power systems. , 2007 .

[12]  R. Das,et al.  Numerical Modeling and Thermal Analysis of an Adsorption Refrigeration System , 2015 .

[13]  M. Venegas,et al.  Experimental study of a thermochemical compressor for an absorption/compression hybrid cycle , 2012 .

[14]  Mohand Tazerout,et al.  Thermodynamic analysis of tri-generation with absorption chilling machine , 2003 .

[15]  Yi Jiang,et al.  Energy utilization evaluation of CCHP systems , 2006 .

[16]  Joel Hernández-Santoyo,et al.  Trigeneration: an alternative for energy savings , 2003 .

[17]  J Hernandez Santoyo,et al.  TRIGENERATION: AN ALTERNATIVE FOR ENERGY SAVINGS , 2003 .

[18]  Abdul Khaliq,et al.  Exergy analysis of gas turbine trigeneration system for combined production of power heat and refrigeration , 2009 .

[19]  Alessandro Franco,et al.  THERMOECONOMIC OPTIMIZATION OF HEAT RECOVERY STEAM GENERATORS OPERATING PARAMETERS FOR COMBINED PLANTS , 2004 .

[20]  Alberto Coronas,et al.  An overview of combined absorption power and cooling cycles , 2013 .

[21]  Z. Sun Experimental investigation of integrated refrigeration system (IRS) with gas engine, compression chiller and absorption chiller , 2008 .

[22]  José Fernández-Seara,et al.  Compression–absorption cascade refrigeration system , 2006 .

[23]  Wenxing Shi,et al.  Absorption heating technologies: A review and perspective , 2014 .

[24]  S. Chungpaibulpatana,et al.  A review of absorption refrigeration technologies , 2001 .

[25]  Ruzhu Wang,et al.  COMBINED COOLING, HEATING AND POWER: A REVIEW , 2006 .

[26]  R. Ventas,et al.  Single-effect absorption refrigeration cycle boosted with an ejector-adiabatic absorber using a single solution pump , 2014 .

[27]  Kamaruzzaman Sopian,et al.  Thermodynamic Analysis of an Ejector-Flash Tank-Absorption Cooling System , 2013 .

[28]  Liming Liu,et al.  Variation and design criterion of heat load ratio of generator for air cooled lithium bromide–water double effect absorption chiller , 2016 .

[29]  Marc A. Rosen,et al.  Exergoeconomic comparison of double effect and combined ejector-double effect absorption refrigeration systems , 2013 .

[30]  Omer Kaynakli,et al.  Energy and exergy analysis of a double effect absorption refrigeration system based on different heat sources , 2015 .

[31]  Petr Stehlík,et al.  Waste to energy – An evaluation of the environmental impact , 2010 .

[32]  Yajun Li,et al.  Exergy-analysis based comparative study of absorption refrigeration and electric compression refrigeration in CCHP systems , 2016 .

[33]  T. K. Gogoi,et al.  Thermodynamic analysis of a combined reheat regenerative thermal power plant and water–LiBr vapor absorption refrigeration system , 2014 .

[34]  Berhane H. Gebreslassie,et al.  Exergy analysis of multi-effect water–LiBr absorption systems: From half to triple effect , 2010 .

[35]  S. C. Kim,et al.  Cycle analysis of an air-cooled LiBr/H2O absorption heat pump of parallel-flow type , 1994 .

[36]  Rin Yun,et al.  Operation Strategy and Parametric Analysis of a CHP and a Tri-Generation System for Integrated Community , 2015 .

[37]  Ilhan Ozturk,et al.  Analysis of compression–absorption cascade refrigeration cycles , 2012 .

[38]  Hongguang Jin,et al.  Thermodynamic analysis of a novel absorption power/cooling combined-cycle , 2006 .

[39]  G. Xu,et al.  Theoretical analysis and optimization of a double-effect parallel-flow-type absorption chiller , 1997 .

[40]  Marc A. Rosen,et al.  Analysis of crystallization risk in double effect absorption refrigeration systems , 2011 .