Side-by-Side Comparisons of Evacuated Compound Parabolic Concentrator and Flat Plate Solar Collector Systems

Three liquid-based solar heating systems employing different types of solar collectors were tested side by side near Chicago, Illinois for one year. The three different types of collectors were: (1) a flat plate collector with a black-chrome coated absorber plate and one low-iron glass cover; (2) an evacuated-tube compound parabolic concentrator (CPC) with a concentration ratio of 1.1, oriented with tubes and troughs along a north-south axis; and (3) an evacuated-tube CPC collector with a concentration ratio of 1.3 and one low-iron glass cover, with tubes and troughs oriented along an east-west axis. Results indicate that the flat plate collector system was the most efficient during warm weather, but the CPC systems were more efficient during cold weather, but the CPC systems were more efficient during cold weather, and the CPC systems operated under conditions too adverse for the flat plate collector. The computer simulation model ANSIM was validated by means of the side-by-side tests. The model uses analytical solutions to the storage energy balance. ANSIM is compared with the general simulation TRNSYS.