Robust algorithm to estimate fault synchrophasor from fault-transient synchrophasor in phasor data concentrator

A fault-transient synchrophasor is computed over a window of pre-fault and fault samples. A fault synchrophasor is computed over a window of fault samples only. Fault-transient synchrophasors are discarded and are generally not used in the synchrophasor applications. Recently, an algorithm has been proposed to compute fault synchrophasor from fault-transient synchrophasor in phasor data concentrator (PDC). The accuracy of the existing algorithm deteriorates due to fault-induced transients and inaccurate fault starting time. A robust algorithm has been proposed to compute fault synchrophasor from fault-transient synchrophasor in PDC. The proposed algorithm does not use fault starting time in the calculations. It also performs better than the existing algorithm when fault-induced transients are present in the signal. The proposed algorithm is simple, non-iterative and performs satisfactorily in various investigated scenarios. The advantage of the proposed algorithm has been demonstrated in the context of fault location application.

[1]  T. Takagi,et al.  Development of a New Type Fault Locator Using the One-Terminal Voltage and Current Data , 1982, IEEE Power Engineering Review.

[2]  Daqing Hou,et al.  Out-of-step protection fundamentals and advancements , 2004, 57th Annual Conference for Protective Relay Engineers, 2004.

[3]  S.M. Brahma,et al.  Fault location scheme for a multi-terminal transmission line using synchronized Voltage measurements , 2005, IEEE Transactions on Power Delivery.

[4]  Sarasij Das,et al.  A new algorithm to compute fault synchrophasor from transient state synchrophasor in PDC , 2013, 2013 IEEE Power & Energy Society General Meeting.

[5]  Sarasij Das,et al.  Algorithms to Improve Performance of Wide Area Measurement Systems of Electric Power Systems , 2014 .

[6]  A.A. Girgis,et al.  Fault location on a transmission line using synchronized Voltage measurements , 2004, IEEE Transactions on Power Delivery.

[7]  E.O. Schweitzer,et al.  Real-Time Power System Control Using Synchrophasors , 2008, 2008 61st Annual Conference for Protective Relay Engineers.

[8]  Ranjana Sodhi,et al.  A transient monitor to reflect the quality of synchrophasors , 2010, IEEE PES General Meeting.

[9]  Ilia Voloh,et al.  An innovative timestamp-based convolution integral method in synchrophasor estimation within digital relays , 2011, 2011 International Conference on Advanced Power System Automation and Protection.