The Characteristic Study of Capacity Control of an Industrial Cooler Using an Invertor Compressor with Varing the Ambient Temperatures

Abstract: The ambient temperature of the experimental conditions changes by varying the speed of the compressor and the electronic expansion valve opening. The effects of changing valve opening to the entire system has been investigat ed. The results show that the ambient temperatures of 35℃ and 30℃ controlled at 30Hz must be avoided. The capacity control range of the control compressor with changing speed is about 43~100% at 35℃, 43~100% at 25℃ and 48~100% at 10℃, respectively. The results show the capacity control range decreases with decreasing ambient temper ature. Key words: Industrial cooler, Inverter, Electronic expansion valve, Superh eat, Capacity control †교신저자(부경대학교 냉동공조공학과, E-mail:yoonji@pknu.ac.kr, Tel: 051-629-6180)1 부경대학교 냉동공조공학과2 (주) 대일 1. 서 론 최신 최첨단 산업기계의 초고속화 및 초정밀화로 인해 산업기계의 구동장치계, 열교환장비, 금형, 제품냉각 등에 필수적으로 열변형방지를 위한 정밀한 온도제어가 가능한 냉각기의 필요성이 요구되고 있다. 이와 같은 요구를 반영하여 저가 제품이면서 온도 정밀도를 어느 정도 높인 핫가스 제어 방법[1-2]을 이용한 산업용 냉각기가 출시되었다. 현재까지 일반적으로 많이 사용되고 있는 공작기계용 냉각기에 적용되어왔던 제어방식은 단순히 전원을 끄고 켜는 방식으로 부하의 변동에 따라 적절하게 용량을 조절하지 못하며 단속운전을 실시함으로써 정밀한 온도제어가 불가능하며 또한 기동시의 소비전력의 증가로 인한 효율감소를 가져왔다. 에어컨인 히트펌프 제품을 중심으로 압축기 회전수 제어에 의한 정밀 온도 및 용량제어에 관한 연구