Four years of experience with silver-copper ionization for control of legionella in a german university hospital hot water plumbing system.

Silver-copper ionization was used for controlling Legionella distribution in a German university hospital hot water plumbing system for 4 years. In the beginning, silver concentrations were not allowed to exceed 10 microg/L because of drinking water regulation limits in Germany. Water samples were monitored for Legionella counts, temperature, and silver and copper concentrations. A significant (P<.001) 3.8-log reduction of Legionella counts, from 40, 000 cfu/L to 7 cfu/L, was found during the first year with silver-copper ionization. Nevertheless, the long-term efficacy of silver concentrations <10 ,++microg/L was not sufficient. Legionella counts increased to 10,000 cfu/L during the third year. During the fourth year, we studied the influence of higher silver concentrations on Legionella distribution. With an average silver level of 30 microg/L, only a 1.3-log reduction in Legionella, to 500 cfu/L, was achieved. The effect was not significant (P=.071); therefore, it must be considered that Legionella developed a tolerance to silver ions.

[1]  Charles P. Gerba,et al.  The molecular mechanisms of copper and silver ion disinfection of bacteria and viruses , 1988 .

[2]  V. Yu,et al.  Individual and combined effects of copper and silver ions on inactivation of Legionella pneumophila , 1996 .

[3]  V. Yu Resolving the Controversy on Environmental Cultures for Legionella : A Modest Proposal , 1998, Infection Control &#x0026; Hospital Epidemiology.

[4]  C. Gerba,et al.  Efficacy of copper and silver ions and reduced levels of free chlorine in inactivation of Legionella pneumophila , 1989, Applied and environmental microbiology.

[5]  E. Wald,et al.  Efficacy of thermal treatment and copper-silver ionization for controlling Legionella pneumophila in high-volume hot water plumbing systems in hospitals. , 1997, American journal of infection control.

[6]  F. Selenka,et al.  [Effect of silver and copper ions on survival of Legionella pneumophila in tap water]. , 1996, Zentralblatt fur Hygiene und Umweltmedizin = International journal of hygiene and environmental medicine.

[7]  V L Yu,et al.  Controlled evaluation of copper-silver ionization in eradicating Legionella pneumophila from a hospital water distribution system. , 1994, The Journal of infectious diseases.

[8]  V L Yu,et al.  Intermittent use of copper-silver ionization for Legionella control in water distribution systems: a potential option in buildings housing individuals at low risk of infection. , 1998, Clinical infectious diseases : an official publication of the Infectious Diseases Society of America.

[9]  R. Slack,et al.  Outbreak of Legionnaires' disease at University Hospital, Nottingham. Epidemiology, microbiology and control , 1993, Epidemiology and Infection.

[10]  P W Muraca,et al.  Disinfection of water distribution systems for legionella: a review of application procedures and methodologies. , 1990, Infection control and hospital epidemiology.