Control Scheme for Three-Phase Four-Wire UPQC in a Three-Phase Stationary Frame

In order to suppress the influences of non-ideal input voltage and non-ideal load, a coordinated control strategy based on ABC stationary frame for three-phase four-wire (3P4W) unified power quality conditioner (UPQC) is introduced. By controlling the series converter as a fundamental sine current source and the parallel converter as a fundamental sine voltage source, the proposed control strategy can make the UPQC carry out all of the control goals: sinusoidal input current with unit power factor, sinusoidal and balanced output voltage with rated value. The experimental results of 10 kVA prototype verify that the control strategy is feasible.

[1]  Sun Yuanzhang Three-phase Unified Power Quality Controller Without Isolating Circuit , 2006 .

[2]  Chen Jian STUDY OF CONTROL STRATEGY FOR A UNIFIED POWER QUALITY CONDITIONER , 2004 .

[3]  Hirofumi Akagi,et al.  The unified power quality conditioner: the integration of series- and shunt-active filters , 1998 .

[4]  Chen Jian STUDY OF CONTROL STRATEGY FOR SERIES-PARALLEL COMPENSATED UPS WITH DOUBLE CONVERTERS , 2003 .

[5]  Jian Chen,et al.  A new control scheme for series-parallel compensated UPS system , 2003, IEEE International Electric Machines and Drives Conference, 2003. IEMDC'03..

[6]  I. Valade,et al.  UPQC reliability analysis , 2002, 10th International Conference on Harmonics and Quality of Power. Proceedings (Cat. No.02EX630).