Histogram-Based Method to Avoid Maloperation of Transformer Differential Protection Due to Current-Transformer Saturation Under External Faults

Current transformer (CT) saturation can cause the maloperation of transformer differential protection under external faults. To avoid this problem, a method based on the histogram of the normalized rotated current (NRC) is proposed. NRC is obtained by a symmetric waveform transformation of a part differential current. An index based on the histogram is defined to evaluate the NRC frequency distribution. The external faults with different degrees of CT saturation, internal faults, and transferring faults can be clearly distinguished by the proposed method. Moreover, the detection time is invariably less than a half cycle after the obvious increase of the differential current. Simulation results validated the proposed method.

[1]  Kuniaki Yabe,et al.  Power differential method for discrimination between fault and magnetizing inrush current in transformers , 1996 .

[2]  J. Faiz,et al.  A novel wavelet-based algorithm for discrimination of internal faults from magnetizing inrush currents in power transformers , 2006, IEEE Transactions on Power Delivery.

[3]  Normann Fischer,et al.  Considerations for Using Harmonic Blocking and Harmonic Restraint Techniques on Transformer Differential Relays , 2011 .

[4]  Majid Sanaye-Pasand,et al.  Power Transformer Protection Using a Multiregion Adaptive Differential Relay , 2014, IEEE Transactions on Power Delivery.

[5]  Majid Sanaye-Pasand,et al.  Development of a new derivative-based algorithm to detect current transformer saturation , 2012 .

[6]  R.P. Maheshwari,et al.  Power Transformer Differential Protection Based On Optimal Probabilistic Neural Network , 2010, IEEE Transactions on Power Delivery.

[7]  Zarko Djekic,et al.  The Impact of Current-Transformer Saturation on Transformer Differential Protection , 2015, IEEE Transactions on Power Delivery.

[8]  M. Djuric,et al.  A new algorithm for avoiding maloperation of transformer differential protection , 2016 .

[9]  M.A. Rahman,et al.  Modeling and protection of a three-phase power transformer using wavelet packet transform , 2005, IEEE Transactions on Power Delivery.

[10]  Ali Hooshyar,et al.  CT Saturation Detection Based on Waveform Analysis Using a Variable-Length Window , 2011, IEEE Transactions on Power Delivery.

[11]  Bin Wang,et al.  Identification of Cross-Country Fault of Power Transformer for Fast Unblocking of Differential Protection , 2009, IEEE Transactions on Power Delivery.

[12]  Alex Y. Wu The Analysis of Current Transformer Transient Response and Its Effect on Current Relay Performance , 1985, IEEE Transactions on Industry Applications.

[13]  D. Jiles,et al.  Theory of ferromagnetic hysteresis , 1986 .

[14]  L. Schiel,et al.  Correction of Current Transformer Transient Performance , 2008, IEEE Transactions on Power Delivery.

[15]  P.A. Crossley,et al.  A CT saturation detection algorithm using symmetrical components for current differential protection , 2006, IEEE Transactions on Power Delivery.

[16]  Xiangning Lin,et al.  Analysis of Electromagnetic Transient and Adaptability of Second-Harmonic Restraint Based Differential Protection of UHV Power Transformer , 2010, IEEE Transactions on Power Delivery.

[17]  Pei Liu,et al.  Self-adaptive transformer differential protection , 2013 .

[18]  B. Kasztenny,et al.  New magnetizing inrush restraining algorithm for power transformer protection , 2001 .

[19]  D. Jiles,et al.  Numerical determination of hysteresis parameters for the modeling of magnetic properties using the theory of ferromagnetic hysteresis , 1992 .

[20]  Linders Transient response of current transformers , 1977, IEEE Transactions on Power Apparatus and Systems.

[21]  Zoran Obradovic,et al.  Training an artificial neural network to discriminate between magnetizing inrush and internal faults , 1994 .

[22]  D Barbosa,et al.  Power Transformer Differential Protection Based on Clarke's Transform and Fuzzy Systems , 2011, IEEE Transactions on Power Delivery.

[23]  S. F. Huang,et al.  A New Algorithm to Avoid Maloperation of Transformer Differential Protection in Substations With an Inner Bridge Connection , 2012, IEEE Transactions on Power Delivery.

[24]  M. S. Sachdev,et al.  Online identification of magnetizing inrush and internal faults in three-phase transformers , 1992 .

[25]  Pei Liu,et al.  Improved operation of differential protection of power transformers for internal faults , 1992 .

[26]  Okan Ozgonenel,et al.  Current transformer modeling for compensating algorithms , 2013, 4th International Conference on Power Engineering, Energy and Electrical Drives.

[27]  Ehab F. El-Saadany,et al.  CT Saturation Detection Based on Waveshape Properties of Current Difference Functions , 2013, IEEE Transactions on Power Delivery.

[28]  Z.Q. Bo,et al.  A new method to identify CT saturation based on the time difference algorithm , 2009, 2009 IEEE Power & Energy Society General Meeting.

[29]  M. Azizur Rahman,et al.  A New Implementation Method of Wavelet-Packet-Transform Differential Protection for Power Transformers , 2010, IEEE Transactions on Industry Applications.

[30]  O. A. S. Youssef,et al.  A wavelet-based technique for discrimination between faults and magnetising inrush currents in transformers , 2002, IEEE Power Engineering Society Summer Meeting,.

[31]  D. W. Nicoletti,et al.  A wavelet-based differential transformer protection , 1999 .

[32]  M. Davarpanah,et al.  Fast and Reliable CT Saturation Detection Using a Combined Method , 2009, IEEE Transactions on Power Delivery.

[33]  Udaya Annakkage,et al.  A current transformer model based on the Jiles-Atherton theory of ferromagnetic hysteresis , 2000 .