Modal Identification and Seismic Performance Evaluation of 154kV Transformer Porcelain Bushing by Vibration Test

The power supply system is one of the most important infrafacilities which should maintain their inherent function during and after earthquakes. This study was performed to analyze dynamic characteristics and seismic performance of Korean typical 154kV transformer porcelain bushing. For the purpose of this study, actual 154kV porcelain bushings were selected and tested on the shaking table. The vibration tests consist of modal identification tests, seismic performance tests, and fragility tests. The sine sweep waves, artificial earthquake waves, and continuous resonant sine waves were used as shaking table motions. This paper describes the test specimens, shaking facilities, and test methods. Natural frequencies and damping ratios of the bushing have been evaluated from the experimental data. The failure mode and the performance level of the Korean transformer bushing have been first identified in this study.