A novel approach to high voltage substation surveillance using radio frequency interference measurement

The deployment of radio frequency interference (RFI) measurement has gained increasing acceptance as a front line, non-invasive technique to assess the condition of individual high-voltage (HV) electrical equipment items as part of a substation surveillance program. However, successful detection and discrimination of low-repetition rate discharges that typically accompany electrical deterioration is constrained by the capabilities and limitations of the field spectrum/RFI analysers used and the electro-magnetic interference (EMI) measurement techniques supported. This paper presents a novel approach to RFI measurement and assessment that is more sensitive to the RFI emissions that typically accompany electrical deterioration and provides more effective discrimination of the discharge phenomena from the ambient frequency spectrum and noise. Case studies from substation surveillance are presented to demonstrate the effectiveness of the approach. The technique is effective with a wide range of HV equipment and is less reliant on expert knowledge for a practicing engineer to confidently characterise and trace electrical deterioration with a high degree of confidence.

[1]  E. Gulski Discharge pattern recognition in high voltage equipment , 1995 .

[2]  W. Schaefer Narrowband and broadband discrimination with a spectrum analyzer or EMI receiver , 2006, 2006 IEEE International Symposium on Electromagnetic Compatibility, 2006. EMC 2006..

[3]  P.J. Moore,et al.  Radiometric location of partial discharge sources on energized high-Voltage plant , 2005, IEEE Transactions on Power Delivery.

[4]  W. Schaefer Understanding impulse bandwidth specifications of EMI receivers , 1999, 1999 IEEE International Symposium on Electromagnetic Compatability. Symposium Record (Cat. No.99CH36261).

[5]  E. N. Limberger Locating radio frequency interference on power transmission lines , 1992, [Proceedings] 1992 Rural Electric Power Conference. Papers presented at the 36th Annual Conference.

[6]  Masayuki Hikita,et al.  Electromagnetic noise spectrum caused by partial discharge in air at high voltage substations , 1998 .

[7]  G. A. Jackson Survey of EMC measurement techniques , 1989 .

[8]  G. Runger,et al.  A theory to optimize the detection and measurement of EMI signals , 1989, National Symposium on Electromagnetic Compatibility.

[9]  W. Janischewskyj,et al.  Micro-Gap Discharge Phenomena and Television Interference , 1985, IEEE Transactions on Power Apparatus and Systems.

[10]  Raj Aggarwal,et al.  Radio frequency measurement of different discharges , 2003, 2003 IEEE Bologna Power Tech Conference Proceedings,.

[11]  M. O. Loftness Power line RF interference-sounds, patterns, and myths , 1997 .

[12]  W. Schaefer Measurement of impulsive signals with a spectrum analyzer or EMI receiver , 2005, 2005 International Symposium on Electromagnetic Compatibility, 2005. EMC 2005..

[13]  Martin D. Judd,et al.  Investigation of partial discharge current pulses in transformer insulating oil , 2001 .

[14]  Michel Duval,et al.  Interpretation of gas-in-oil analysis using new IEC publication 60599 and IEC TC 10 databases , 2001 .