Evaporation heat transfer and pressure drop characteristics of R-600a in horizontal smooth and helically dimpled tubes

In the present study, condensation heat transfer and frictional pressure drops of refrigerant R-600a (iso-butane) inside a helically dimpled tube and a plain tube of internal diameter 8.3 mm were measured and analyzed. All tests were performed at different vapor qualities up to 0.82 and average saturation temperatures ranging between 38 and 42 °C. Refrigerant mass fluxes varied in the range of 114–368 kg/m2 s. The inner surface of the helically dimpled tube has been designed and reshaped through three-dimensional material surface modifications consists of both shallow and deep protrusions which are placed evenly in helical directions on the tube wall. The experimental results show that the heat transfer coefficients of the dimpled tube are 1.2–2 times of those in smooth tube with a pressure drop penalty just ranging between 58% and 195. The highest heat transfer coefficient is occurred at vapor quality of 0.53 and mass flow rate of 368 kg/m2 s. On the other hand, the maximum increase of pressure drop takes place at vapor quality of 0.55 and mass flow rate of 368 kg/m2 s.

[1]  L. Friedel Improved Friction Pressure Drop Correlation for Horizontal and Vertical Two-Phase Pipe Flow , 1979 .

[2]  E. Garcia,et al.  Heat transfer performance enhancement in compact heat exchangers by using shallow square dimples in flat tubes , 2016 .

[3]  S. Wongwises,et al.  Condensation heat transfer and flow characteristics of R-134a flowing through corrugated tubes , 2011 .

[4]  C. Aprea,et al.  Comparison of R407C and R417A heat transfer coefficients and pressure drops during flow boiling in a horizontal smooth tube , 2008 .

[5]  B. Sundén,et al.  Condensation and evaporation heat transfer characteristics in horizontal smooth, herringbone and enhanced surface EHT tubes , 2015 .

[6]  S. J. Kline,et al.  Describing Uncertainties in Single-Sample Experiments , 1953 .

[7]  K. Gungor,et al.  A general correlation for flow boiling in tubes and annuli , 1986 .

[8]  Shuli Liu,et al.  A comprehensive review on passive heat transfer enhancements in pipe exchangers , 2013 .

[9]  Jinliang Xu,et al.  Condensation heat transfer of R245fa in tubes with and without lyophilic porous-membrane-tube insert , 2015 .

[10]  Wei Li,et al.  Comparison of tubeside condensation and evaporation characteristics of smooth and enhanced heat transfer 1EHT tubes , 2015 .

[11]  J. Thome,et al.  Heat transfer, pressure drop, and flow pattern recognition during condensation inside smooth, helical micro-fin, and herringbone tubes , 2007 .

[12]  A. Cavallini,et al.  Heat transfer and pressure drop during condensation of refrigerants inside horizontal enhanced tubes , 2000 .

[13]  Anirudh Gupta Review of Heat Transfer Augmentation Through Different Passive Intensifier Methods , 2012 .

[14]  P. Bansal,et al.  Characteristics of condensing and evaporating heat transfer using hydrocarbon refrigerants , 2006 .

[15]  T. Teng,et al.  Retrofit assessment of refrigerator using hydrocarbon refrigerants , 2014 .

[16]  Z. Ayub,et al.  Geometric optimization for thermal–hydraulic performance of dimpled enhanced tubes for single phase flow , 2016 .

[17]  Jinliang Xu,et al.  Modulated heat transfer tube with short conical-mesh inserts: A linking from microflow to macroflow , 2015 .

[18]  Sukumar Devotta,et al.  Simulated and experimental performance of split packaged air conditioner using refrigerant HC-290 as a substitute for HCFC-22 , 2014 .

[19]  E. Al-Hajri,et al.  Single phase heat transfer and pressure drop analysis of a dimpled enhanced tube , 2016 .

[20]  J. Thome Enhanced Boiling Heat Transfer , 1990 .

[21]  Wei Li,et al.  Comparison of condensation and evaporation heat transfer on the outside of smooth and enhanced 1EHT tubes , 2016 .

[22]  H. K. Varma,et al.  Experimental study of heat transfer augmentation versus pumping power in a horizontal R12 evaporator , 1991 .

[23]  T. Newell,et al.  Heat transfer and pressure drop during condensation of refrigerant 134a in an axially grooved tube , 1999 .

[24]  Gustaaf Jacobs,et al.  Thermo-Fluid Dynamics of Two-Phase Flow , 2013 .

[25]  John R. Thome,et al.  Flow boiling in horizontal smooth tubes: New heat transfer results for R-134a at three saturation temperatures , 2009 .

[26]  M. Chandrasekar,et al.  Experimental studies on heat transfer and friction factor characteristics of CuO/water nanofluid under turbulent flow in a helically dimpled tube , 2011 .

[27]  M. Molina,et al.  Stratospheric sink for chlorofluoromethanes: chlorine atomc-atalysed destruction of ozone , 1974, Nature.

[28]  Qing Liu,et al.  Effects of rib geometries and property variations on heat transfer to supercritical water in internally ribbed tubes , 2015 .

[29]  S. M. Ghiaasiaan TWO-PHASE FLOW, BOILING AND CONDENSATION IN CONVENTIONAL AND MINIATURE SYSTEMS , 2007 .

[30]  A. Greco,et al.  Convective boiling of pure and mixed refrigerants: An experimental study of the major parameters affecting heat transfer , 2008 .

[31]  S. Zivi Estimation of Steady-State Steam Void-Fraction by Means of the Principle of Minimum Entropy Production , 1964 .

[32]  J. Thome,et al.  Condensation in horizontal tubes, part 2: new heat transfer model based on flow regimes , 2003 .

[33]  A. Miyara,et al.  Condensation heat transfer of herringbone micro fin tubes , 2002 .

[34]  A. Cavallini,et al.  Condensation in Horizontal Smooth Tubes: A New Heat Transfer Model for Heat Exchanger Design , 2006 .

[35]  D. Kukulka,et al.  Thermal-hydraulic performance of Vipertex 1EHT enhanced heat transfer tubes , 2013 .