A case study of ground source direct cooling system integrated with water storage tank system

Energy consumption for the commercial buildings has increasingly gained attentions, due to the significant electricity consumption and peak power demand. To solve this problem, this paper focuses on performance on the Ground Source Direct Cooling (GSDC) system integrated with a Water Storage Tank System (WSTS) in the summer, which directly utilizes the low-grade energy to supply high temperature water for the radiant floor cooling system and make full use of the electric rate difference between on-peak and off-peak periods. In summer, the indoor air temperature is controlled between 23 and 26 °C, resulting in a comfortable thermal environment. The total cooling capacities in 2014 and 2015 were 32.6 kWh/m2 and 30.7 kWh/m2, respectively. The annual energy consumptions for Electricity Unit Intensity (EUI) in 2014 and 2015 were 33.0 kWh/(m2·yr) and 32.1 kWh/(m2·yr), and the cooling energy consumptions only consumed 4.19 kWh/(m2·yr) and 4.55 kWh /(m2·yr), respectively. The annual operating cost of this cooling system only reaches 9 yuan/(m2·yr) through the analysis of 5 years’ operation. Compared to a conventional air cooled heat pump system, this cooling system has a larger initial cost, but its recovery period is less than 4.3 years, due to the extremely low operating cost. Overall, this GSDC system integrated with WSTS in the summer has remarkable advantages in thermal comfort and energy efficiency.

[1]  Kang Zhao,et al.  Application of radiant floor cooling in large space buildings – A review , 2016 .

[2]  Boqiang Lin,et al.  China's building energy efficiency and urbanization , 2015 .

[3]  Alessandro Beghi,et al.  Energy efficient control of HVAC systems with ice cold thermal energy storage , 2014 .

[4]  Corina Stetiu,et al.  Energy and peak power savings potential of radiant cooling systems in US commercial buildings , 1999 .

[5]  Jianlei Niu,et al.  A review of the application of radiant cooling & heating systems in Mainland China , 2012 .

[6]  Bing Dong,et al.  A real-time model predictive control for building heating and cooling systems based on the occupancy behavior pattern detection and local weather forecasting , 2013, Building Simulation.

[7]  Lei Yong Experimental Study of A Free Cooling System Using Soil as Heat Sink in Shanghai , 2012 .

[8]  Nora El-Gohary,et al.  Energy-related values and satisfaction levels of residential and office building occupants , 2016 .

[9]  Zhaoxia Wang,et al.  An occupant-based energy consumption prediction model for office equipment , 2015 .

[10]  Jie Lin,et al.  Simplified thermal calculation method for floor structure in radiant floor cooling system , 2014 .

[11]  Helmut E. Feustel,et al.  Hydronic radiant cooling — preliminary assessment☆ , 1995 .

[12]  Zhao Li-qian Experimental study on ground temperature variation characteristics of a ground-sink direct cooling system , 2009 .

[13]  Kwang Woo Kim,et al.  A 50 year review of basic and applied research in radiant heating and cooling systems for the built environment , 2015 .

[14]  Chao Chen,et al.  Analytical solution for heat transfer in a multilayer floor of a radiant floor system , 2014 .

[15]  Xiaohua Liu,et al.  Cooling Performance Comparison of Radiant Floor System and All-air System with Solar Radiation☆ , 2015 .

[16]  Per Heiselberg,et al.  Validation and modification of modeling thermally activated building systems (TABS) using EnergyPlus , 2014 .

[17]  Eusébio Z. E. Conceição,et al.  Comfort and airflow evaluation in spaces equipped with mixing ventilation and cold radiant floor , 2013 .

[18]  Yufeng Zhang,et al.  Numerical analysis of three direct cooling systems using underground energy storage: A case study of Jinghai County, Tianjin, China , 2012 .

[19]  Weifeng Zhu,et al.  Experimental study of a ground sink direct cooling system in cold areas , 2009 .

[20]  Celina Filippín,et al.  Transient simulation of a storage floor with a heating/cooling parallel pipe system , 2010 .