Analysis on Parameters Selection of Injection Circuit of Differentiation Cascade type Controllable Custom Power Quality Disturbance-Generator

Theoretical and simulated analysis on the injection circuit parameters of the Controllable Custom Power Quality Disturbance-Generator which is designed as differentiation cascade type has been done. The topology has three modules: fundamental-frequency module, high-frequency module and rectifier module. The theoretical analysis results have shown that the regulation precision of output of the fundamental-frequency module, the voltage level of the high-frequency module, the current tracking performance and the harmonic current circumfluence in the high frequency module will be influenced by the linking inductor of the fundamental-frequency module. The harmonic current output of the high-frequency module will be influenced by the linking inductor of the high-frequency module. Furthermore, taking a capacitor in series with the inductor in the injection circuit of the high-frequency module is an effective method to reduce the voltage level of the high-frequency module. However, this method will influence the amount of the fundamental frequency current that generated by fundamental-frequency module. The simulations have been carried out to show the correctness of the theoretical analysis and provide a reference for parameters selection of the injection circuit and the design of the device's control methods.