Frost retardation of an air-source heat pump by the hot gas bypass method

This study is concerned with a hot gas (refrigerant) bypass method to retard the formation and propagation of frost in an air-source heat pump. The feasibility of the hot gas bypass method was investigated experimentally and the method's performance is compared with that of a normal, 1.12 kW capacity air-source heat pump system with no defrost equipment such as an electric resistance heater. Results indicate that the hot gas bypass method is useful for retarding the formation and growth of frost at the outdoor coil. The best performance is shown under a bypass refrigerant flow rate of 0.2 kg/min (20% of the whole system refrigerant flow rate). During 210 min of heat pump operation, the hot gas bypass method improved COP and heating capacity at an average of 8.5% and 5.7%, respectively, relative to the normal system.

[1]  P. G. Jolly,et al.  A comparison of hot-gas by-pass and suction modulation method for partial load control in refrigerated shipping containers , 2001 .

[2]  Syed M. Zubair,et al.  Thermodynamic analysis of capacity-control schemes for refrigeration and air-conditioning systems , 1996 .

[3]  Gordian Associates Heat pump technology : a survey of technical developments, market prospects and research needs , 1980 .

[4]  Honghyun Cho,et al.  Performance of a showcase refrigeration system with multi-evaporator during on–off cycling and hot-gas bypass defrost , 2005 .

[5]  Syed M. Zubair,et al.  Performance evaluation of hot-gas by-pass capacity control schemes for refrigeration and air-conditioning systems , 2000 .

[6]  Syed M. Zubair,et al.  SECOND-LAW-BASED THERMODYNAMIC ANALYSIS OF HOT- GAS, BY-PASS, CAPACITY-CONTROL SCHEMES FOR REFRIGERATION AND AIR-CONDITIONING SYSTEMS , 1995 .

[7]  W. A. Miller,et al.  Laboratory examination and seasonal analysis of frosting and defrosting for an air-to-air heat pump , 1987 .

[8]  Viung C. Mei,et al.  A Frost-Less Heat Pump , 2002 .

[9]  D. O’Neal,et al.  Frost/defrost performance of a three-row fin staged heat pump evaporator. , 2002 .

[10]  Dennis L. O'Neal,et al.  Frosting performance of tube fin heat exchangers with wavy and corrugated fins , 1991 .

[11]  Haji Hassan Masjuki,et al.  Testing and rating non-ducted air conditioners in Malaysia: The applicability of ISO standard 5151 , 2002 .

[12]  Takao Nishimura,et al.  “Heat pumps — status and trends” in Asia and the Pacific , 2002 .

[13]  Billy C. Langley Heat Pump Technology , 1983 .

[14]  Mark O. McLinden,et al.  NIST Thermodynamic and Transport Properties of Refrigerants and Refrigerant Mixtures-REFPROP , 1998 .