Identification of grid impedance for purposes of voltage feedback active filtering
暂无分享,去创建一个
A voltage feedback active filter is vulnerable to unknown grid impedance. To overcome this problem we propose an identification method, which uses the control system of a frequency selective active filter to measure the grid impedance at selected frequencies. The usefulness of the method is experimentally demonstrated with a 19 kVA active rectifier with a voltage feedback active filtering function. The voltage feedback active filtering is performed in a case in which the active filter control is not stable before the impedance is identified with the method proposed. It is shown that the use of the measured grid impedance in the control system greatly enhances the dynamic stability of the system. Also, the grid impedance measurements are provided in two cases.