Characterizing transportation of indoor gaseous contaminant using the state space method

Abstract This paper employs the state space method to characterize transportation of indoor gaseous pollutant in steady airflow field. From the differential equations governing contaminant transportation in space, the state space equation for transportation is proposed and the analytical solution is obtained. In the method, the matrix covering hologram of the transportation is derived. The state space equation is validated with the analytic solution for the case of the simultaneous transportation of the pollution for piston flow. Similarly, the concentration from the proposed method for a 2-D case also agrees well with the result from CFD method based on the experimentally validated flow field. Based upon the analytic solution of the state equation, it is easily known that the influence of the initial concentration distribution and the pollution source on the concentration at the specific point. In addition, assisted by Chen’s zero equation turbulence model [1] , the concentration field for a 3-D case is simulated by the presented method. It is found that there exists a regular stage at which the relative effect of the initial concentration distribution and the source on the concentration field will not change with time.

[1]  Yinping Zhang,et al.  Simulation of VOC emissions from building materials by using the state-space method , 2009 .

[2]  S. Kato,et al.  Distribution of chemical pollutants in a room based on CFD simulation coupled with emission/sorption analysis , 2001 .

[3]  Zhang Yinping,et al.  Spatial flow influence factor: A novel concept for indoor air pollutant control , 2006 .

[4]  Ashok J. Gadgil,et al.  Indoor pollutant mixing time in an isothermal closed room: An investigation using CFD , 2003 .

[5]  Yi Jiang,et al.  An integrated modeling tool for simultaneous analysis of thermal performance and indoor air quality in buildings , 2008 .

[6]  S. Patankar Numerical Heat Transfer and Fluid Flow , 2018, Lecture Notes in Mechanical Engineering.

[7]  Y. Jiang,et al.  State-space method for the calculation of air-conditioning loads and the simulation of thermal behavior of the room , 1982 .

[8]  Qingyan Chen,et al.  A zero-equation turbulence model for indoor airflow simulation , 1998 .

[9]  Mats Sjöberg,et al.  The use of moments for assessing air quality in ventilated rooms , 1983 .

[10]  Ying Xu,et al.  An improved mass transfer based model for analyzing VOC emissions from building materials , 2003 .

[11]  Szu-Chieh Chen,et al.  Compartmental Human Respiratory Tract Modeling of Airborne Dust Exposure from Feeding in Swine Buildings , 2004, Journal of the Air & Waste Management Association.

[12]  Min Li,et al.  State-space model for airborne particles in multizone indoor environments , 2008 .

[13]  Bin Zhao,et al.  Prediction of transient contaminant dispersion and ventilation performance using the concept of accessibility , 2004 .

[14]  S. Kato New Scales for Evaluating Ventilation Efficiency as Affected by Supply and Exhaust Opening Based on Spatial Distribution of Contaminant , 1992 .

[15]  Xudong Yang,et al.  Total air age: an extension of the air age concept , 2003 .

[16]  C. Liao Use of residence time distribution for evaluation of gaseous pollutant volatilization from stored swine manure. , 1997, Journal of environmental science and health. Part. B, Pesticides, food contaminants, and agricultural wastes.

[17]  Zhiqiang John Zhai,et al.  Evaluation of Various Turbulence Models in Predicting Airflow and Turbulence in Enclosed Environments by CFD: Part 2—Comparison with Experimental Data from Literature , 2007 .

[18]  J. Sundell,et al.  On the history of indoor air quality and health. , 2004, Indoor air.

[19]  Cleve B. Moler,et al.  Nineteen Dubious Ways to Compute the Exponential of a Matrix, Twenty-Five Years Later , 1978, SIAM Rev..

[20]  H. Brenner The diffusion model of longitudinal mixing in beds of finite length. Numerical values , 1995 .