Evaluation of Condensation Prevention for Centralized Hybrid Ventilation System Using TDR

Purpose: Condensation in the apartment housing is one of the most significant defects and complaints for condensation are rapidly increasing according to the growing interest in residential environment. Korea government established a regulation for reducing condensation in the apartment housing and TDR is adapted as a standard. However prevention of condensation depend on improving the performance of building envelop has limitation because of the increase of the cost. Centralized Hybrid ventilation system is suggested to prevent condensation. Method: Field measurement was conducted to verify the ventilation rate of the ventilation system. Based on the measurement, air network and CFD simulation was conducted to analyze ventilation rate for each room. Surface temperature was calculated by regulated TDR according to the regions and surfaces. The performance of condensation prevention was evaluated by the ventilation rate and surface temperature. Result: In the results, it was found that condensation was prevented in more than 90% of households by the centralized hybrid ventilation system which provided 0.19 ~ 0.81ACH for each room.