A Research into a Device for Measuring the Electric Power Quality and the Harmonic Frequency
暂无分享,去创建一个
The harmonic frequency occurred in a power system causes errors and failures of equipments such as motors, and an unnecessary power consumption. The fundamental countermeasure for the harmonic frequency is to eliminate the cause of the harmonic frequency. This paper describes about making the device to figure out the cause in real time, verifying the operation of the device, and utilizing it to various power quality measurements. The power usually has the line frequency between 45Hz and 66Hz. In this research, the number of the harmonic frequencies which can be analysed inside the 2.8kHz bandwidth, the filter bandwidth of ADE7880, is 2800/f, and the maximum is 2800/45 = 63. The maximum order of the harmonic frequency in Korea, which has the line frequency of 60Hz, was measured as 2800/60 = 46th. Also, the accuracy of the voltage, current, and power measurement had the error within 0.1%, confirming that it is very precise.