Study on Seismic Analysis and Test for Seismic Qualification of 245kV GIS
暂无分享,去创建一个
Gas insulated switchgear is large-sized electric equipment for providing a reliable supply of electric power. Recently, seismic tests of electric equipment using a shaking table have been mandated because seismic performance has become an increasingly important issue. However, basic analysis methods continue to be used because some electric equipment is too large for shaking table facilities. Thus, a reliable analysis method should be developed for large-scale electric equipment. This study aims to evaluate the seismic qualification of a 245kV GIS in accordance with IEEE-693 and to validate the analysis method by comparing it with test results. Both the test and the analysis showed that the 245kV GIS has proper seismic safety. Furthermore, the differences between the analysis and the test results are less than 10% for an accurately given mass, stiffness, and input acceleration. It is expected that this study can be used for the seismic qualification of large-scale electrical structures.
[1] V. Rees,et al. Verification of the seismic resistance of gas-insulated switchgear (GIS) , 1991 .
[2] Heung-Tae Kim,et al. Seismic and Structure Analysis of a Temporary Rack Construction in a Nuclear Power Plant , 2011 .
[3] Yoshinori Shimizu,et al. Gas insulated switchgear developed to meet increased load demand in Los Angeles Basin , 2010, IEEE PES T&D 2010.
[4] Boo-Youn Lee,et al. Dynamic Analysis and Structural Safety Evaluation of the Cabinet of a Reactor Safety System , 2005 .