Derivative Method Based Orientation Detection of Substation Grounding Grid

The grounding grid is a key part of substation protection, which provides safety to personnel and equipment under normal as well as fault conditions. Currently, the topology of a grounding grid is determined by assuming that its orientation is parallel to the plane of earth. However, in practical scenarios, the assumed orientation may not coincide with the actual orientation of the grounding grid. Hence, currently employed methods for topology detection fails to produce the desired results. Therefore, accurate detection of grounding grid orientation is mandatory for measuring its topology accurately. In this paper, we propose a derivative method for orientation detection of grounding grid in high voltage substations. The proposed method is applicable to both equally and unequally spaced grounding grids. Furthermore, our method can also determine the orientation of grounding grid in the challenging case when a diagonal branch is present in the mesh. The proposed method is based on the fact that the distribution of magnetic flux density is perpendicular to the surface of the earth when a current is injected into the grid through a vertical conductor. Taking the third order derivative of the magnetic flux density, the main peak coinciding with the position of underground conductor is accurately obtained. Thus, the main peak describes the orientation of buried conductor of grounding grid. Simulations are performed using Comsol Multiphysics 5.0 to demonstrate the accuracy of the proposed method. Our results demonstrate that the proposed method calculate the orientation of grounding grid with high accuracy. We also investigate the effect of varying critical parameters of our method.

[1]  Hu Xue Research on Corrosion and Protection of Grounding Grid , 2002 .

[2]  Wang Xiaoyu,et al.  Topological measurement and characterization of substation grounding grids based on derivative method , 2014 .

[3]  Qian Wang,et al.  A Novel Method for Fault Diagnosis of Grounding Grids , 2015, IEEE Transactions on Industry Applications.

[4]  Xingzhe Hou,et al.  Break point diagnosis of grounding grids using transient electromagnetic apparent resistivity imaging , 2015, 2015 IEEE Power & Energy Society General Meeting.

[5]  Z. Zhu,et al.  A Hybrid Field Model for Open-Circuit Field Prediction in Surface-Mounted PM Machines Considering Saturation , 2018, IEEE Transactions on Magnetics.

[6]  Sponsor,et al.  IEEE guide for safety in AC substation grounding , 2013 .

[7]  Karsten Ahnert,et al.  Numerical differentiation of experimental data: local versus global methods , 2007, Comput. Phys. Commun..

[8]  Zhihong Fu,et al.  Configuration Detection of Substation Grounding Grid Using Transient Electromagnetic Method , 2017, IEEE Transactions on Industrial Electronics.

[9]  Wei He,et al.  Topology Measurement of Substation's Grounding Grid by Using Electromagnetic and Derivative Method , 2016 .

[10]  Xizi Song,et al.  A hybrid regularization method combining Tikhonov with total variation for electrical resistance tomography , 2015 .

[11]  B. Zhang,et al.  Diagnosis of breaks in substation's grounding grid by using the electromagnetic method , 2002 .

[12]  Xiaoyan Xu,et al.  Reconstruction of substation grounding grid based on concept of regret , 2016, 2016 IEEE International Conference on High Voltage Engineering and Application (ICHVE).

[13]  Y. Leong Yeow,et al.  A general method of computing the derivative of experimental data , 2006 .

[14]  Shizhe Song,et al.  STUDY ON THE ELECTROCHEMICAL SENSING SYSTEMFOR MONITORING/DETECTING MARINE STEEL CORROSION , 2009 .

[15]  W. Xiaoyu,et al.  A Derivative-Based Method for Buried Depth Detection of Metal Conductors , 2018, IEEE Transactions on Magnetics.

[16]  Gang Xu,et al.  Optimization algorithm of corrosion diagnosis for grounding grid , 2010, 2010 2nd International Conference on Mechanical and Electronics Engineering.

[17]  Asanka S. Rodrigo,et al.  Safety in AC substation grounding systems under transient conditions: Development of design software , 2013, 2013 IEEE 8th International Conference on Industrial and Information Systems.

[18]  Xiaokuo Kou,et al.  A Cycle Voltage Measurement Method and Application in Grounding Grids Fault Location , 2017 .

[19]  Fusheng Wang,et al.  A simulation method on fault diagnosis : Grounding grids , 2010, 2010 2nd International Conference on Advanced Computer Control.

[20]  W. F. Thompson,et al.  Application of higher derivative techniques to analysis of high-resolution thermal denaturation profiles of reassociated repetitive DNA. , 1978, Proceedings of the National Academy of Sciences of the United States of America.

[21]  F. A. Orakzai,et al.  BREAKPOINT DIAGNOSIS OF SUBSTATION GROUNDING GRID USING DERIVATIVE METHOD , 2017 .

[22]  Peng Wang,et al.  A New Optimization Algorithm for Grounding Grid Fault Diagnosis , 2008, 2008 International Workshop on Modelling, Simulation and Optimization.