A Module Based Active Noise Control System for Ventilation Systems, Part II : Performance Evaluation

To utilize the full noise attenuation potential of an active noise control (ANC) system applied to duct noise, it is important to be able to minimize the turbulence induced noise in the microphone signals. This is the second paper in a series of two, that treats the problem of turbulence induced noise originating from the airflow inside the ducts, when applying ANC to ducts. Part I contains theoretical and experimental investigations of the influence of the turbulence induced noise on the filtered-x LMS algorithm used in the ANC system. Part II (the present paper) is concerned with design and investigations of microphone installations which produces a sufficient amount of turbulence suppression while also meeting industry requirements. These requirements are, for example, that the microphone installations should be based on standard ventilation parts, and that they should be easily installed and maintained. Furthermore, results concerning the performance of an ANC system with different microphone installations are presented. Some of the results were obtained at an acoustic laboratory according to an ISO standard. The attenuation achieved with ANC was approximately 15-25 dB between 50-315 Hz even for airflow speeds up to 20 m/s.

[1]  Lars Håkansson,et al.  Microphone Windscreens for Turbulent Noise Suppression when Applying Active Noise Control to Ducts , 2005 .

[2]  Henry P. Bakewell Narrow‐Band Investigations of the Longitudinal Space‐Time Correlation Function in Turbulent Airflow , 1964 .

[3]  M. Nishimura,et al.  Some Problems of Active Noise Control for Practical Use , 1991 .

[4]  W. Neise,et al.  The flow noise level at microphones in flow ducts , 1979 .

[5]  A. Cabelli,et al.  The influence of turbulent pressure fluctuations on an active attenuator in a flow duct , 1989 .

[6]  M. O. Tokhi,et al.  Active noise control systems , 1987 .

[7]  Akira Nakamura,et al.  Experimental Investigation for Detection of Sound‐Pressure Level by a Microphone in an Airstream , 1971 .

[8]  Lars Håkansson,et al.  A Module Based Active Noise Control System for Ventilation Systems, Part I : Influence of Measurement Noise on the Performance and Convergence of the Filtered-x LMS Algorithm , 2009 .

[9]  Don H. Johnson,et al.  Array Signal Processing: Concepts and Techniques , 1993 .

[10]  I. C. Shepherd,et al.  Microphone screens for acoustic measurement in turbulent flows , 1986 .

[11]  Ml Munjal,et al.  An exact one‐dimensional analysis of the acoustic sensitivity of the antiturbulence probe tube in a duct , 1989 .

[12]  M. Crocker,et al.  Tubular windscreen design for microphones for in‐duct fan sound power measurements , 1974 .

[13]  Sen M. Kuo,et al.  Active Noise Control , 2008 .

[14]  W. Neise,et al.  Theoretical and experimental investigations of microphone probes for sound measurements in turbulent flow , 1975 .

[15]  S. C. Southward,et al.  Active Control of Noise and Vibration , 1996 .