Proper Orthogonal Decomposition-Based Modeling Framework for Improving Spatial Resolution of Measured Temperature Data

This paper presents a proper orthogonal decomposition (POD)-based reduced-order modeling framework to improve spatial resolution of measured temperature data in an air-cooled data center. This data-driven approach is applied on transient air temperature data, acquired at the exhaust of a server simulator rack. Temperature data is collected by a distributed thermocouple network at 1 Hz sampling frequency following a step impulse in the rack heat load. The input data are organized in a 2-D array, comprising transient temperature signals measured at various spatial locations. Because its computational time scales logarithmically with the input size, the proposed POD-based approach is potentially useful as an efficient tool for handling large transient data sets. With spatial location being the parameter for the input data matrix, the proposed approach is suitable for rapid synthesis of transient temperature data at new spatial locations. The comparison between POD-based local air temperature predictions and corresponding data indicates a maximum prediction uncertainty of 3.2%, and root mean square prediction uncertainty of 1.9%.

[1]  Graham Martin Nelson,et al.  Development of an Experimentally-Validated Compact Model of a Server Rack , 2007 .

[2]  A. Abdel-azim Fundamentals of Heat and Mass Transfer , 2011 .

[3]  P. Holmes,et al.  The Proper Orthogonal Decomposition in the Analysis of Turbulent Flows , 1993 .

[4]  S. Rippa,et al.  Data Dependent Triangulations for Piecewise Linear Interpolation , 1990 .

[5]  R. F. Sullivan Alternating Cold and Hot Aisles Provides More Reliable Cooling for Server Farms , 2000 .

[6]  Yogendra Joshi,et al.  Error estimation in POD-based dynamic reduced-order thermal modeling of data centers , 2013 .

[7]  Mia Hubert,et al.  Robust PCA and classification in biosciences , 2004, Bioinform..

[8]  Farrokh Mistree,et al.  An Approach to Robust Design of Turbulent Convective Systems , 2006 .

[9]  H Moon,et al.  Computational and Performance Aspects of PCA-Based Face-Recognition Algorithms , 2001, Perception.

[10]  P. Guibert,et al.  Use of proper orthogonal decomposition for time interpolation from PIV data , 2005 .

[11]  Chung-Kuo Chang,et al.  Video surveillance for hazardous conditions using sensor networks , 2004, IEEE International Conference on Networking, Sensing and Control, 2004.

[12]  Nathan Wayne Rolander An Approach for the Robust Design of Data Center Server Cabinets , 2005 .

[13]  Vanish Talwar,et al.  Monalytics: online monitoring and analytics for managing large scale data centers , 2010, ICAC '10.

[14]  M. Iyengar,et al.  Rapid Three-Dimensional Thermal Characterization of Large-Scale Computing Facilities , 2008, IEEE Transactions on Components and Packaging Technologies.

[15]  L. Sirovich Turbulence and the dynamics of coherent structures. II. Symmetries and transformations , 1987 .

[16]  Robert J. Moffat,et al.  Describing the Uncertainties in Experimental Results , 1988 .

[17]  Richard E. Brown,et al.  Report to Congress on Server and Data Center Energy Efficiency: Public Law 109-431 , 2008 .

[18]  Yogendra Joshi,et al.  Multi-parameter model reduction in multi-scale convective systems , 2010 .

[19]  Yi Ma,et al.  Robust principal component analysis? , 2009, JACM.

[20]  Philipp Birken,et al.  Numerical Linear Algebra , 2011, Encyclopedia of Parallel Computing.

[21]  Frank Bellosa,et al.  Energy Management for Hypervisor-Based Virtual Machines , 2007, USENIX Annual Technical Conference.

[22]  Luiz André Barroso,et al.  The Price of Performance , 2005, ACM Queue.

[23]  Yogendra Joshi,et al.  Proper Orthogonal Decomposition for Reduced Order Thermal Modeling of Air Cooled Data Centers , 2010 .