Numerical experiments in fire science: a study of ceiling jets

In this paper, a numerical experiment, consisting of 90 simulations in Fire Dynamics Simulator (FDS), is conducted for two different purposes. Firstly, numerical experiments are explored as a research method in fire science, and it is demonstrated that numerical experiments could be used as a complement to traditional fire experiments in fire science research. Secondly, an evaluation of previously derived correlations for ceiling jet excess temperatures and velocities is performed with the help of the results from the numerical experiment. The procedure used in this evaluation constitutes an outline for how a numerical experiment can be conducted in fire science. The evaluation indicates that the existing correlations will give a good estimate of the average temperature in a ceiling jet calculated by FDS. However, the correlations do not give a good estimate of the maximum excess temperature. A new correlation to estimate the maximum temperature has therefor been developed and is presented in the paper (Less)

[1]  Bart Merci,et al.  Verification of the accuracy of CFD simulations in small-scale tunnel and atrium fire configurations , 2011 .

[2]  R. L. Alpert Turbulent Ceiling-Jet Induced by Large-Scale Fires , 1975 .

[3]  Kevin B McGrattan Evaluation of fire models for nuclear power plant applications :: benchmark exercise #3 : international panel report , 2007 .

[4]  C. H. Marks,et al.  Characterizing The Unconfined Ceiling Jet Under Steady-state Conditions: A Reassessment , 1991 .

[5]  Robert L Vettori Effect of beamed, sloped, and sloped beamed ceilings on the activation time of a residential sprinkler , 2003 .

[6]  Kevin B. McGrattan,et al.  Verification and Validation of Selected Fire Models for Nuclear Power Plant Applications. Volume 2. Experimental Uncertainty (NUREG 1824) | NIST , 2007 .

[7]  R. L. Alpert Calculation of response time of ceiling-mounted fire detectors , 1972 .

[8]  Guillermo Rein,et al.  Travelling fires for structural design-Part II: Design methodology , 2012 .

[9]  E Braun,et al.  Temperature Uncertainties for Bare-Bead and Aspirated Thermocouple Measurements in Fire Environments , 2003 .

[10]  Wan Ki Chow,et al.  Correlation equations on fire-induced air flow rates through doorway derived by large eddy simulation , 2005 .

[11]  Glenn P. Forney,et al.  CFAST – Consolidated Model of Fire Growth and Smoke Transport (Version 7) Volume 2: User’s Guide , 2015 .

[12]  Glenn P. Forney,et al.  Fire Dynamics Simulator (Version 3): User's Guide (NISTIR 6784) | NIST , 2001 .

[13]  Bart Merci,et al.  CFD study of relation between ventilation velocity and smoke backlayering distance in large closed car parks , 2012 .