Performance of Medium Voltage Overhead Distribution Lines Against Lightning Discharges

SUMMARY The lightning discharges are one of the main causes of interruptions of medium voltage overhead distribution lines, being the reason of great concern for the utility companies. Its destructive effects frequently extends to equipments and connected installations, with the possibility to cause personal injuries and material damages, beyond economic losses, due to out of income and the possibility of indemnities, penalties and fines. With the beginning of the deregulation of the electric energy supply, some actions were been taken by the utilities for the prevention and minimization of the damages associated to the lightning discharges. However, as the lightning discharges are random events, consequently, difficult to predict, the majority of these actions does not follow a study or a detailed analysis of the problem. By this way, in the majority of the cases the actions were taken based on the knowledge of the engineer in charge, or based in rules defined without any effective evidence, by means of studies or by laboratory tests. As a result, many of them besides of presenting high cost are not effective. Among others, the distribution network reliability depends directly on its exposition to the lightning discharges. To determine the exposition level of the line, the designer should know the number of discharges to the ground per unit of area per unit of time. The aim of this paper is to present the results of the performance study of medium voltage overhead distribution lines against lightning discharges, in the way to define methodologies to reduce the system failures. The results were obtained within the partnership among the High Voltage Laboratory of the Federal University of Itajuba, AES Sul Utility Company and the University of Bologna. Direct discharges and induced surges were simulated into real networks to identify the major factor of influence for network failures. Then commentaries on the relative performance and comparisons of different construction configurations of overhead lines are presented. Once that the atmospheric discharges phenomena are random, this work considers that the parameter generation of the discharges follows the statistical data proposed by Anderson and Eriksson. The Monte Carlo Method is used for the incidence distribution of the discharges and the Electro Geometrical Model for the interception point of the discharge.

[1]  M. Paolone,et al.  An Improved Procedure for the Assessment of Overhead Line Indirect Lightning Performance and Its Comparison with the IEEE Std. 1410 Method , 2007, IEEE Transactions on Power Delivery.

[2]  C. de Salles,et al.  Insulation coordination for a 23 kV medium voltage distribution , 2003, 2003 IEEE Bologna Power Tech Conference Proceedings,.

[3]  Mario Paolone,et al.  Performance of Medium Voltage Overhead Distribution Lines Against Lightning-Induced Voltages: A Comparative Analysis , 2006 .

[4]  M. Ianoz,et al.  Transient analysis of multiconductor lines above a lossy ground , 1999 .

[5]  H. Elahi,et al.  Modeling guidelines for fast front transients , 1996 .

[6]  M. Ianoz,et al.  Lightning-induced voltages on overhead lines , 1993 .

[7]  Ashok K. Agrawal,et al.  Transient Response of Multiconductor Transmission Lines Excited by a Nonuniform Electromagnetic Field , 1980 .

[8]  Farhad Rachidi,et al.  A new finite difference time domain scheme for the evaluation of lightning induced overvoltage on multiconductor overhead lines , 2001 .

[9]  P. Chowdhuri,et al.  Estimation of Flashover Rates of Overhead Power Distribution Lines by Lightning Strokes to Nearby Ground , 1989, IEEE Power Engineering Review.

[10]  M. Ianoz,et al.  Lightning-induced voltages on an overhead line above a lossy ground: a sensitivity analysis , 1996 .

[11]  Mario Paolone,et al.  Statistical Evaluation of Lightning Performances of Distribution Lines , 2001 .

[12]  M. Ianoz,et al.  Influence of a lossy ground on lightning-induced voltages on overhead lines , 1996 .