The purpose of this study is on the evaluations of the energy saving effects by cogeneration system in the view
point of its operating methods and building needs. The followings are the results of this study. ①6 building needs
(apartment, office, hospital, hotel, department, and complex(hotel+department)) are specified and every each hourly
cooling, heating and electricity loads and heat-electricity ratio(HER) also are calculated. In apartment, monthly and
hourly HERs are scattered, and in office, monthly HER is converged but hourly is scattered. But in hotel, monthly and
hourly HERs are all converged. ②The operating methods are specified and energy flow diagram is completed. And also
energy saving equations are introduced from the diagram. As the result of computational evaluation, ③the most expected
energy saving effect is happened at the condition of apartment with fuel-cell type cogeneration operating by heat-loads
following method. ④With heat-electricity balance operation, hotel and hospital is expected as highly effect of energy
saving. ⑤In the most cases, fuel-cell type cogeneration system shows the highest energy saving effect. ⑥This study
recommends, the most effective operating method for apartment is heat-loads following operating method, for office is
electricity-loads following method. And for hotel, it depends on the cogeneration system.