Effects of unbalanced voltage on the operation performance of a three-phase induction motor

This paper uses a real load test to investigate the effects of an unbalanced voltage supply on an induction motor's performance. Based upon various experiments, including: (1) cases with the same unbalance voltage factor but different unbalanced voltages; (2) cases with only one unbalanced voltage but different degrees of unbalance; and (3) cases with the same positive-sequence voltage but different negative-sequence voltages, the importance of the positive-sequence voltage in the motor's apparent performance and of the negative-sequence voltage in the hidden damage are pointed out. Finally, it is strongly suggested that the related regulations, and a motor's derating factor and temperature rise curves should be based on not only a voltage unbalance factor, but also the magnitude of the positive-sequence voltage.

[1]  B. N. Gafford,et al.  Heating of Induction Motors on Unbalanced Voltages , 1959, Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems.

[2]  Elham B. Makram,et al.  Starting transients of induction motors connected to unbalanced networks , 1989 .

[3]  Paul B. Cummings,et al.  Protection of Induction Motors Against Unbalanced Voltage Operation , 1985, IEEE Transactions on Industry Applications.

[4]  M. M. Berndt,et al.  Derating of polyphase induction motors operated with unbalanced line voltages , 1962, Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems.