Fire-induced pressure and smoke spreading in mechanically ventilated buildings with air-tight envelopes

Abstract Fire-induced pressures have not been considered dangerous in building fires, but the situation may be changing as building envelopes become increasingly air-tight. In this study, we investigate whether this can change the fire development and pose new risks for structural and evacuation safety. We used experiments to validate the numerical models, and models for simulating the fire development in buildings with different air-tightness levels. The simulations considered air permeability values typical for traditional, modern and Near-Zero buildings. Three different smoke damper configurations were studied, and the fire growth rates were varied from medium to ultra-fast. The results showed that transitioning from traditional and modern buildings to Near-Zero buildings can sufficiently increase the peak overpressures from fast-growing fires to cause structural damage. Conditions were identified for avoiding excessively high overpressures, while preventing smoke from spreading through the ventilation system.

[1]  Christian Delvosalle,et al.  Comparison of Fire Hazards in Passive and Conventional Houses , 2012 .

[2]  Per Blomqvist,et al.  Emissions from Fires Part II: Simulated Room Fires , 2004 .

[3]  Jason Floyd COUPLING A NETWORK HVAC MODEL TO A COMPUTATIONAL FLUID DYNAMICS MODEL USING LARGE EDDY SIMULATION , 2011 .

[4]  Laurent Audouin,et al.  Doorway Flows Induced by the Combined Effects of Natural and Forced Ventilation in Case of Multi-compartments Large-Scale Fire Experiments , 2016 .

[5]  Frederick W. Mowrer Enclosure Smoke Filling and Fire-Generated Environmental Conditions , 2016 .

[6]  Patrick Van Hees,et al.  Validation of FDS for large-scale well-confined mechanically ventilated fire scenarios with emphasis on predicting ventilation system behavior , 2013 .

[7]  M. Röwekamp,et al.  OECD PRISME project: Fires in confined and ventilated nuclear-type multi-compartments - Overview and main experimental results , 2013 .

[8]  S. Hostikka,et al.  Experiments and Numerical Simulations of Pressure Effects in Apartment Fires , 2017 .

[9]  Jose L. Torero,et al.  SFPE handbook of fire protection engineering , 2016 .

[10]  J. Floyd,et al.  Computational fluid dynamics modelling of fire , 2012 .

[11]  Hugues Pretrel,et al.  Pressure variations induced by a pool fire in a well-confined and force-ventilated compartment , 2012 .

[12]  J. M. Such,et al.  Effect of ventilation procedures on the behaviour of a fire compartment scenario , 2005 .

[13]  Jarek Kurnitski,et al.  Airtightness of residential buildings in Finland , 2015 .