Abstract
Objective:
To investigate the safety of the hospital water supply following a major flood.
Design:
Surveillance was conducted of the hospital water supply as it entered the hospital and at randomly selected water faucets throughout the facility.
Setting:
A newly constructed surgical critical-care unit in a 265-bed community hospital that had to be evacuated and was out of operation for 6 weeks following a major flood of the city.
Methods:
Random water samples throughout the facility were analyzed for heterotrophic plate counts (HPCs), chlorine, and coliforms utilizing standard methods.
Results:
Water samples entering the hospital met appropriate standards, indicating the city water distribution system was not contaminated. Of 169 faucets tested, 13 (22%) of 59 electronic faucets exceeded the HPC threshold, and 12 (11%) of 110 manual faucets exceeded the HPC threshold (P<.14). A comparison of two brands of electronic faucets with manual faucets and with each other revealed that the HPC threshold was exceeded by 11 (32%) of 34 brand A faucets as compared to 12 (11%) of 110 manual faucets (P<.006). The HPC threshold was exceeded by 2 (8%) of 25 brand B faucets compared to 12 (11%) of 110 manual faucets (P<.94). Contamination rates of brand A and brand B faucets differed significantly (P<.003). Similar testing 2 months after hyperchlorination of the water supply indicated that the HPC threshold was exceeded by 16 (52%) of 31 brand A faucets compared to 10 (9.%) of 110 manual faucets (P<.0000003) and by 2 (18%) of 25 brand B faucets compared to 10 (9%) of 110 manual faucets (P=1.0).
Conclusions:
A certain brand of electronic water faucet used in the hospital was associated with unacceptable levels of microbial growth in water and was a continuing source of bacteria potentially hazardous to patients.
[1]
G. Pugliese,et al.
Risk Factors for Antibiotic-Resistant E coli Isolated From UTI Patients
,
2001,
Infection Control & Hospital Epidemiology.
[2]
R. A. Deininger.
Maintaining a Disinfectant Residual in the Distribution System
,
2000
.
[3]
Awwa,et al.
Standard Methods for the examination of water and wastewater
,
1999
.
[4]
E. Maubec,et al.
Multi-resistant Pseudomonas aeruginosa outbreak associated with contaminated tap water in a neurosurgery intensive care unit.
,
1998,
The Journal of hospital infection.
[5]
W. Rutala,et al.
Water as a Reservoir of Nosocomial Pathogens
,
1997,
Infection Control & Hospital Epidemiology.
[6]
J. Rose,et al.
Risk assessment of opportunistic bacterial pathogens in drinking water.
,
1997,
Reviews of environmental contamination and toxicology.
[7]
J. Rose,et al.
Health significance of pigmented bacteria in drinking water
,
1997
.
[8]
D. Lye,et al.
Virulence characteristics of heterotrophic bacteria commonly isolated from potable water
,
1993
.
[9]
A. E. Greenberg,et al.
Standard methods for the examination of water and wastewater : supplement to the sixteenth edition
,
1988
.
[10]
Cooke Em,et al.
The fate of ingested Pseudomonas aeruginosa in normal persons.
,
1969
.
[11]
A. C. Buck,et al.
The fate of ingested Pseudomonas aeruginosa in normal persons.
,
1969,
Journal of medical microbiology.