Local Dynamic Similarity Model of Cross-Ventilation Part 1 - Theoretical Framework
暂无分享,去创建一个
Abstract A new model has been proposed for evaluating the discharge coefficient and flow angle at an inflow opening for cross-ventilation. This model is based on the fact that the cross-ventilation flow structure in the vicinity of an inflow opening creates dynamic similarity under the condition that the ratio of the cross-ventilation driving pressure to the dynamic pressure of cross flow at the opening is consistent. It was confirmed, from a wind tunnel experiment, that the proposed model can be applied regardless of wind direction and opening position. Change of pressure along the stream tube of a cross-ventilated flow was estimated from the results of Large Eddy Simulation, and was set as the basis of model preparation. It was found that the static pressure at the opening was exhausted by the flow‘s acceleration and by turbulent kinetic energy generation during this stage.
[1] R. M. Aynsley. A resistance approach to estimating airflow through buildings with large openings due to wind , 1988 .
[2] Per Heiselberg,et al. Principles of hybrid ventilation. , 2002 .
[3] B. J. Vickery,et al. External wind pressure distributions and induced internal ventilation flow in low-rise industrial and domestic structures , 1987 .
[4] S. Murakami,et al. Development of a new k−ε model for flow and pressure fields around bluff body , 1997 .