Influence of normalization in dynamic reactive load models
暂无分享,去创建一个
As an extension of previous studies on modeling and identification of nonlinear dynamic load models, this letter describes the influence of the normalization in dynamic reactive load models. Using measured data from normal operation, it is shown that the reactive power level, which has previously used as normalization factor is inappropriate. If instead apparent power level is used, the variability in the parameters that describe the reactive load response is drastically reduced.
[1] D. Hill,et al. Modelling and identification of nonlinear dynamic loads in power systems , 1994 .
[2] David J. Hill,et al. Nonlinear dynamic load models with recovery for voltage stability studies , 1993 .
[3] Ping Ju,et al. Nonlinear dynamic load modelling: model and parameter estimation , 1996 .
[4] C. W. Taylor. Power System Voltage Stability , 1993 .