Purpose
The DELTA® beam composite floor system is a recently developed shallow floor type that has seen many applications in contemporary construction. It involves partially encasing DELTA® steel beams in concrete, with the lower flange remaining exposed. Besides the satisfactory behavior of the system at ambient conditions, understanding its response under elevated temperatures is critical in evaluating its overall performance. Despite certification from the manufacturing company that the system has adequate fire resistance, its behavior under fire conditions has neither been investigated to depth nor reported in detail. The purpose of this paper is the detailed numerical investigation of their behavior in fire. For this reason, the finite element method was implemented in this paper to simulate the response of such beams subjected to fire. Material properties were modeled according to the Eurocodes. The coupled thermal-structural parametric analyses involved four different variations of the “shortest” and “deepest” cross-section (eight case studies in total) specified by the manufacturing company. Other simulations of these cross-sections, in which either the thermal expansion or the structural load were not taken into account, were carried out for comparison purposes.
Design/methodology/approach
The methodology for simulating such systems, which has been successfully implemented and validated against fire test results elsewhere (Maraveas et al., 2012) was also followed here. To investigate the statement made by Maraveas et al. (2014) and the equations proposed by Zaharia and Franssen (2012) that the insulation is not so effective for “short” cross-sections, two beams, one with a D20-200 (Deltabeam Technical Manual, 2013) cross-section (shallowest section) and one with a D50-600 (Deltabeam Technical Manual, 2013) cross-section (deepest section), were simulated in this paper for comparison purposes. Additionally, reasonable assumptions were made for the cross-sectional dimensions not specified by the manufacturer (Deltabeam Technical Manual, 2013) and parametric analyses were carried out to investigate their effect on the structural response of the system.
Findings
Composite DELTA® beams can achieve fire resistances ranging from 120 to 180 min, depending on the depth and geometry of their cross-section, with deeper sections displaying a better fire response. The intense thermal bowing that occurs when these beams are heated from below has a more pronounced effect, in terms of thermally induced deflections for deeper sections. The satisfactory fire resistance of these beams is achieved due to the action of the concrete encased web and the reinforcement which compensate for the loss of the exposed lower flange. Increasing the thickness of the web in deeper sections improves their fire rating up to 180 min. The thickness of the lower flange affects the fire rating of the beams only in a minor way.
Practical/implications
The paper describes a numerical methodology to estimate the fire resistance of complex flooring systems.
[1]
K. F. Chung,et al.
Composite column design to Eurocode 4 : based on DD ENV 1994-1-1: 1994 Eurocode 4: design of composite steel and concrete structures: part 1.1: general rules and rules for buildings
,
1994
.
[2]
Ehab Ellobody.
Nonlinear behaviour of unprotected composite slim floor steel beams exposed to different fire conditions
,
2011
.
[3]
C. Maraveas,et al.
Fire Resistance of Unprotected Ultra Shallow Floor Beams (USFB): A Numerical Investigation
,
2017
.
[4]
Chrysanthos Maraveas,et al.
A detailed methodology for the finite element analysis of asymmetric slim floor beams in fire
,
2012
.
[5]
Chrysanthos Maraveas,et al.
Fire resistance of 19th century fireproof flooring systems: A sensitivity analysis
,
2014
.
[6]
Ulf Wickström,et al.
Comments on calculation of temperature in fire-exposed bare steel structures in prEN 1993-1-2: Eurocode 3—design of steel structures—Part 1–2: general rules—structural fire design
,
2005
.
[7]
Chrysanthos Maraveas.
NUMERICAL ANALYSIS OF DELTA COMPOSITE BEAMS IN FIRE
,
2014
.
[8]
Zhongcheng Ma,et al.
Fire resistance of composite slim floor beams
,
2000
.
[9]
Colin Bailey.
The behaviour of asymmetric slim floor steel beams in fire
,
1999
.
[10]
Yong Wang,et al.
Moment capacity of cast-iron beams exposed to fire
,
2016
.
[11]
Jean-Marc Franssen,et al.
Simple equations for the calculation of the temperature within the cross-section of slim floor beams under ISO Fire
,
2012
.
[12]
G. M. Newman.
Fire resistance of slim floor beams
,
1995
.