Study on insulation characteristics of GIS under combined voltage of DC and lightning impulse

Operating experience shows that residual DC voltage remains in GIS bus bar for a long time after opening of disconnectors. This DC voltage will not only cause accumulation of charges and contaminants on the insulator surface, but will also easily lead to motion of free metallic particles in SF6 gas gap, weakening the insulation ability of GIS. At the time of disconnectors reclosing, impulse voltage could be generated in the bus bar and superimpose on the pre-existing DC voltage. As a result, GIS will be under combined voltage of DC and impulse. This paper experimentally studies the insulation characteristics of GIS under combined voltage of DC and lightning impulse. It is found that, for non-contaminated insulators, when DC and LI voltage are of the same polarity, flashover voltage under combined voltage is nearly the same as the flashover voltage under LI alone. However, when they are of the opposite polarity, flashover voltage decreases with increasing DC voltage. In cases there are metallic particle or powder around insulator, pre-stressed DC voltage will cause adhesion of contaminants on the insulator surface and lead to decrease of flashover voltage. Specially, for the particle-contaminated insulator, it is found that the surface charge accumulation caused by DC voltage will have big influence on the flashover voltage, and the most critical condition is when DC and LI voltage are of the opposite polarity. In addition, the breakdown characteristics of SF6 gas gap with free metallic particle are investigated. It is found that under pre-stressed DC voltage, particle will do standing motion or bouncing motion. And breakdown voltage becomes lowest when particle is doing standing motion. The results of the experiments show that residual DC voltage in GIS could deteriorate its insulation ability and the combined voltage of DC and impulse is found to be a critical condition for GIS insulation. Moreover, the combined voltage is shown to be more sensitive to detect some insulation defects in GIS than applying impulse voltage alone, especially for free metallic particles, which are commonly found in GIS but up to now no effective detection method is proposed. Therefore combined voltage of DC and impulse could be considered to serve as a supplement of field test for GIS.

[1]  A. Qureshi,et al.  A Review of Particle-Contaminated Gas Breakdown , 1981, IEEE Transactions on Electrical Insulation.

[2]  C. M. Cooke,et al.  Charging of Insulator Surfaces by Ionization and Transport in Gases , 1981, IEEE Transactions on Electrical Insulation.

[3]  Y. Shibuya,et al.  Surface Charging On Epoxy Spacer At Dc Stress In Compressed SF6 GAS , 1983, IEEE Transactions on Power Apparatus and Systems.

[4]  W. Zaengl,et al.  A Numerical Analysis of Accumulated Surface Charge on DC Epoxy Rrsin Spaces , 1987, IEEE Transactions on Electrical Insulation.

[5]  K. D. Srivastava,et al.  Mechanism of prebreakdown spacer charging in non-uniform fields under unidirectional voltages , 1990 .

[6]  T. Nitta,et al.  Charge accumulation on insulating spacers for HVDC GIS , 1991 .

[7]  O. Farish,et al.  Charging mechanisms of polymer spacers electrically stressed in SF/sub 6/ environment , 1992, [Proceedings] 1992 Annual Report: Conference on Electrical Insulation and Dielectric Phenomena.

[8]  Predrag Osmokrovic,et al.  Numerical and experimental design of three-electrode spark gap for synthetic test circuits , 1994 .

[9]  O. Farish,et al.  Investigations of surface charging of DC insulator spacers , 1995, Proceedings of Conference on Electrical Insulation and Dielectric Phenomena - CEIDP '96.

[10]  Xie Jun,et al.  The influence of surface charge upon flash-over of particle-contaminated insulators in under impulse-voltage conditions , 1997 .

[11]  K. Feser,et al.  The accumulation of surface charge due to a conducting particle on a spacer , 1999 .

[12]  Stefan Tenbohlen,et al.  The influence of surface charge on lightning impulse breakdown of spacers in SF/sub 6/ , 2000 .

[13]  Shigemitsu Okabe,et al.  Wire Particle Motion Behavior and Breakdown Characteristics around Different Shaped Spacers within Diverging Air Gap , 2003 .

[14]  A. Moukengue Imano,et al.  The influence of the dielectric strength of the N/sub 2//SF/sub 6/-insulation by conducting particle on the spacer surface , 2003 .

[15]  Junya Suehiro,et al.  Motion behavior and deactivation method of free-conducting particle around spacer between diverging conducting plates under DC voltage in atmospheric air , 2003 .

[16]  S. Okabe,et al.  Charge distribution measurement on a truncated cone spacer under DC voltage , 2004, IEEE Transactions on Dielectrics and Electrical Insulation.

[17]  Qiu Yu-chang STUDY OF CHARGE ACCUMULATION ON INSULATOR SURFACE IN HVDC GAS-INSULATED SWITCHGEAR , 2005 .

[18]  S. Okabe,et al.  Phenomena and mechanism of electric charges on spacers in gas insulated switchgears , 2007, IEEE Transactions on Dielectrics and Electrical Insulation.

[19]  B. Loncar,et al.  The Validity of the Similarity Law for the Electrical Breakdown of $\hbox{SF}_{6}$ Gas , 2007, IEEE Transactions on Plasma Science.

[20]  S. Okabe,et al.  Evaluation of breakdown characteristics of gas insulated switchgears for non-standard lightning impulse waveforms under diverse conditions , 2008, IEEE Transactions on Dielectrics and Electrical Insulation.

[21]  Predrag Osmokrovic,et al.  Reliability of three-electrode spark gaps , 2008 .

[22]  K. Stanković,et al.  Conditions for the applicability of the geometrical similarity law to impulse breakdown in gases , 2010, IEEE Transactions on Dielectrics and Electrical Insulation.

[23]  Bo Qi,et al.  Surface discharge initiated by immobilized metallic particles attached to gas insulated substation insulators: process and features , 2011, IEEE Transactions on Dielectrics and Electrical Insulation.

[24]  Akiko Kumada,et al.  Influence of tiny metal particles on charge accumulation phenomena of GIS model spacer in high-pressure SF6 gas , 2013, IEEE Transactions on Dielectrics and Electrical Insulation.

[25]  Shigemitsu Okabe,et al.  Insulation characteristics of GIS insulators under lightning impulse with DC voltage superimposed , 2015, IEEE Transactions on Dielectrics and Electrical Insulation.

[26]  Can Guo,et al.  Follow phenomenon of breakdown voltage in SF6 under lightning impulse , 2016, IEEE Transactions on Dielectrics and Electrical Insulation.