Resonances and overvoltages in a medium voltage fan motor drive with long cables in an underground mine

Underground mining is characterized by space constraints forcing the use of long cables to feed large machines, where the application of variable speed drives can generate overvoltages at the machine terminals. This paper presents the analysis and mitigation of harmful overvoltages detected in inverter-fed 1400 HP 13.8 KV motors used for air ventilation in an underground mine. The possible causes of the overvoltages, namely wave reflection and resonance are described theoretically and simulated. On-site direct voltage measurements at the 13.8 kV motor terminals confirmed that resonance was the dominant phenomenon. Based on this study a suitable low-pass filter was designed, constructed and installed. Finally, the adequate operation of such filter is demonstrated by further on-site measurements.

[1]  Shesha H. Jayaram,et al.  High divider ratio fast response capacitive dividers for high voltage pulse measurements , 1995, IAS '95. Conference Record of the 1995 IEEE Industry Applications Conference Thirtieth IAS Annual Meeting.

[2]  R. L. Doughty,et al.  Cost effective motor surge capability , 1995 .

[3]  Alessandro Ferrero,et al.  Measuring equipment for the electric quantities at the terminals of an inverter-fed induction motor , 1996 .

[4]  Peter W. Hammond,et al.  Enhancing the reliability of modular medium-voltage drives , 2002, IEEE Trans. Ind. Electron..

[5]  R. Bodega,et al.  Partial discharge detection using oscillating voltage at different frequencies , 2002, IMTC/2002. Proceedings of the 19th IEEE Instrumentation and Measurement Technology Conference (IEEE Cat. No.00CH37276).

[6]  M. Berth,et al.  Switching overvoltages in motor circuits , 2001 .

[7]  A. von Jouanne,et al.  Filtering techniques to minimize the effect of long motor leads on PWM inverter fed AC motor drive systems , 1995, IAS '95. Conference Record of the 1995 IEEE Industry Applications Conference Thirtieth IAS Annual Meeting.

[8]  N. K. Ghai Design and application considerations for motors in steep fronted surge environments , 1995, Industry Applications Society 42nd Annual Petroleum and Chemical Industry Conference.

[9]  R. A. Hanna,et al.  Medium voltage adjustable speed drives-users' and manufacturers' experiences , 1996, Proceedings of 1996 IAS Petroleum and Chemical Industry Technical Conference.

[10]  E. Persson,et al.  Transient effects in application of PWM inverters to induction motors , 1991, Conference Record of 1991 Annual Pulp and Paper Industry Technical Conference.

[11]  David Leggate,et al.  Interaction of drive modulation and cable parameters on AC motor transients , 1996, IAS '96. Conference Record of the 1996 IEEE Industry Applications Conference Thirty-First IAS Annual Meeting.

[12]  A. von Jouanne,et al.  Design considerations for an inverter output filter to mitigate the effects of long motor leads in ASD applications , 1997 .

[13]  T.A. Lipo,et al.  High frequency modeling for cable and induction motor overvoltage studies in long cable drives , 2001, Conference Record of the 2001 IEEE Industry Applications Conference. 36th IAS Annual Meeting (Cat. No.01CH37248).