Single-tuned Passive Harmonic Filter Design Considering Variances of Tuning and Quality Factor

AbstractThis paper presents how to select tuning factor and quality factor in designing of a single-tuned passive harmonic filter. Tuning factor and quality factor must be considered before a decision of filter parameters(R, L and C). In literature, the study about these two factors has not been performed and only empirical values have been used in the passive harmonic filter design so far. As an empirical value, in cases of 5th and 7th filter, tuning order has been used 4.8th and 6.8th respectively and quality factor has been used in a range of 30 and 60; therefore, we will propose how to decide these two factors in this paper. If a single-tuned passive harmonic filter were off-tuned, its performance would be deteriorated substantially and resulted in a parallel resonance between grid inductance and filter capacitance. In order to avoid this side effect from off-tuning, the filter must be tuned on some preceded order not on the exact order. In other words, total filter impedance must have reactive impeda...

[1]  H. Wayne Beaty,et al.  Electrical Power Systems Quality , 1995 .

[2]  H. Akagi,et al.  A practical approach to harmonic compensation in power systems-series connection of passive and active filters , 1990, Conference Record of the 1990 IEEE Industry Applications Society Annual Meeting.

[3]  H. Akagi,et al.  A new approach to harmonic compensation in power systems , 1988, Conference Record of the 1988 IEEE Industry Applications Society Annual Meeting.

[4]  Ramasamy Natarajan Power System Capacitors , 2005 .

[5]  J. K. Phipps A transfer function approach to harmonic filter design , 1997 .

[6]  P. Mehta,et al.  Active power filters: a review , 2000 .