Lightning Protection of 500-kV DC Gas-Insulated Lines (GIL) With Integrated Surge Arresters

A 500-kV dc hybrid transmission line consisting of a gas-insulated line (GIL) with lengths up to 10 km connected at both ends to long overhead lines is applied for lightning overvoltage studies. For this system, the conventional application of external surge arresters results in high electrical stress on the insulation of GIL. Therefore and because of the modular structure of GIL, the application of internal surge arresters and two combinations of external and integrated surge arresters are investigated. The influence on the voltage buildup in GIL of variation in the position of integrated surge arresters is explained and the best positions are calculated by a sensitivity study. All variants of the application of integrated surge arresters result in a reduction of voltage stress within the GIL compared to the conventional application of external surge arresters.

[1]  J. H. Hagenguth Shielding of transmission lines , 1941, Electrical Engineering.

[2]  Mustafa Kizilcay,et al.  Lightning Overvoltage Analysis for a 380-kV Gas-Insulated Line near a Substation , 2016 .

[3]  A. Rajapakse,et al.  Location of DC line faults in conventional HVDC systems with segments of cables and overhead lines using terminal measurements , 2012, 2012 IEEE Power and Energy Society General Meeting.

[4]  E. R. Whitehead,et al.  Field and Analytical Studiesof Transmission LineShielding , 1968 .

[5]  Hermann Koch,et al.  Insulation co-ordination for gas-insulated transmission lines (GIL) , 2000, 2000 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.00CH37077).

[6]  R. Witzmann,et al.  Modeling techniques for lightning overvoltage analysis using the example of gas insulated transmission lines (GIL) , 2013, 2013 IEEE 1st International Conference on Condition Assessment Techniques in Electrical Systems (CATCON).

[7]  J. A. Martinez,et al.  Surge protection of underground distribution cables , 2000 .

[8]  P. N. Mikropoulos,et al.  Impulse Resistance of Concentrated Tower Grounding Systems Simulated by an ATPDraw Object , 2011 .

[9]  T. Henriksen,et al.  Maximum lightning overvoltage along a cable protected by surge arresters , 2005, IEEE Transactions on Power Delivery.

[10]  P. Pinceti,et al.  A simplified model for zinc oxide surge arresters , 1999 .

[11]  E. W. Greenfield Transient Behavior of Short and Long Cables , 1984, IEEE Power Engineering Review.

[12]  Hermann Koch Gas insulated transmission lines - GIL , 2008, T&D 2008.

[13]  A. Ametani,et al.  A method of a lightning surge analysis recommended in Japan using EMTP , 2005, IEEE Transactions on Power Delivery.

[14]  H. Elahi,et al.  Modeling guidelines for fast front transients , 1996 .

[15]  E. R. Whitehead,et al.  Field and Analytical Studies of Transmission Line Shielding: Part , 1968 .

[16]  P. Chowdhuri,et al.  Parameters of lightning strokes: a review , 2005, IEEE Transactions on Power Delivery.

[17]  Marjan Popov,et al.  Lightning Induced Overvoltages in Mixed 380 kV OHL-Cable-OHL connections , 2013 .

[18]  Zacharias G. Datsios,et al.  Effects of simulation models of overhead transmission line basic components on backflashover surges impinging on GIS substations , 2010, 45th International Universities Power Engineering Conference UPEC2010.

[19]  Pantelis N Mikropoulos,et al.  Estimation of Lightning Incidence to Overhead Transmission Lines , 2010, IEEE Transactions on Power Delivery.

[20]  Volker Hinrichsen Metal-Oxide Surge Arresters in high-voltage power systems: Fundamentals , 2001 .