Single-Phase Adaptive Reclosure of EHV Transmission Lines Based on Shunt Reactor Current Identification

Aiming at EHV transmission lines with shunt compensators, a novel technique is proposed to distinguish fault nature according to low frequency components in faulted phase current of reactor at the recovery voltage stage. In order to identify the magnitude of low frequency components, a energy function is defined which can determine the fault nature in 2~4 fundamental cycles rapidly and accurately. The characteristics of faulted phase current are analyzed in detail. For a permanent fault, the current contains power frequency and decaying slowly DC components. While for a transient fault, the current contains power frequency and low frequency components. Theoretical analysis and EMTP simulation prove that the proposed identification scheme can distinguish the fault nature exactly and improve the success rate of reclosure significantly.

[1]  Du Xiao-gong AN ADAPTIVE VOLTAGE COMPENSATION CRITERION FOR PERMANENT FAULTIN THE SINGLE PHASE AUTOMATIC RE-CLOSING BASED ON FAULT LOCATION , 2004 .

[2]  Yuan Xiao,et al.  Prediction methods for preventing single-phase reclosing on permanent fault , 1989 .

[3]  A. T. Johns,et al.  Improved techniques for modelling fault arcs an faulted EHV transmission systems , 1994 .

[4]  Liu Hai-feng An Adaptive Single-phase Auto-reclosure Scheme Based on Morphological Close-opening-open-closing Gradient (COOCG) Transform , 2005 .

[5]  Mustafa Kizilcay,et al.  Interaction of the secondary arc with the transmission system during single-phase autoreclosure , 2003, 2003 IEEE Bologna Power Tech Conference Proceedings,.

[6]  E. Rosolowski,et al.  Arc effect on single-phase reclosing time of a UHV power transmission line , 2004, IEEE Transactions on Power Delivery.

[7]  Zeng Zhi-an THE STUDY ON SINGLE-POLE ADAPTIVE RECLOSURE OF EHV TRANSMISSION LINES WITH THE SHUNT REACTOR , 2004 .

[8]  Zhao Yan SINGLE-PHASE ADAPTIVE AUTO-RECLOSURE BASED ON FUZZY NEURAL NETWORK , 2005 .

[9]  Eugeniusz Rosolowski,et al.  Arc effect on single-phase reclosing time of a UHV power transmission line , 2004 .

[10]  Liu Jun-ling A New Criterion for Single-phase Adaptive Automatic Reclosure Based on Improved Correlation Algorithm , 2007 .

[11]  A. T. Johns,et al.  Design and implementation of an adapative single pole autoreclosure technique for transmission lines using artificial neural networks , 1996 .

[12]  Jiao Zaibin Identification of Permanent Faults for Single-phase Auto-redosure on Transmission Lines with Shunt Reactors , 2006 .