Impact mechanism of different fill layout patterns on the cooling performance of the wet cooling tower with water collecting devices

This paper deals with the impact mechanism of different fill layout patterns on the cooling performance of the wet cooling tower with water collecting devices (WCTWCD). A 3D numerical model for the WCTWCD is established and validated. The non-uniform layout fill for the WCTWCD is firstly proposed and analyzed. The differences of the performance parameters caused by the different fill layout patterns are studied. Studies in the paper indicate that the uniform layout fill is not the best layout pattern for the WCTWCD. The non-uniform layout fill can enhance the tower cooling performance in both windless and crosswind conditions. To evaluate the ventilation uniformity inside the tower the circumferential coefficient and the radial coefficient are proposed by the author. The air flow field in the tower with non-uniform layout fill is more stable and uniform. The coupling of the air flow field and the fill consumption in the tower with non-uniform layout fill is more reasonable. At last the comparison of the non-uniform layout fill between the conventional wet cooling tower (CWCT) and the WCTWCD is presented.

[1]  Wenqiang Huang,et al.  Comparative study on the cooling characteristics of high level water collecting natural draft wet cooling tower and the usual cooling tower , 2016 .

[2]  Zhu Song Impact of Fill Non-uniform Layout on Cooling Performance of Large-scale Cooling Towers , 2013 .

[3]  Detlev G. Kröger,et al.  Loss coefficient correlation for wet-cooling tower fills , 2003 .

[4]  Adam Klimanek,et al.  Numerical Modelling of Natural Draft Wet-Cooling Towers , 2013 .

[5]  William Hultz Walker,et al.  Principles of chemical engineering , 1923 .

[6]  Lyu Dongqiang,et al.  Experimental study on the air flow field in the water collecting devices , 2016 .

[7]  Adam Klimanek,et al.  A 3D CFD MODEL OF A NATURAL DRAFT WET-COOLING TOWER , 2009 .

[8]  Masud Behnia,et al.  Comparison of a 2D axisymmetric CFD model of a natural draft wet cooling tower and a 1D model , 2008 .

[9]  Srinivas Garimella,et al.  Achieving near-water-cooled power plant performance with air-cooled condensers , 2016 .

[10]  Ming Gao,et al.  Influence of non-uniform layout fillings on thermal performance for wet cooling tower , 2016 .

[11]  J. C. Kloppers,et al.  A critical evaluation and refinement of the performance prediction of wet-cooling towers , 2003 .

[12]  Detlev G. Kröger,et al.  A critical investigation into the heat and mass transfer analysis of counterflow wet-cooling towers , 2005 .

[13]  J. C. Kloppers,et al.  The Lewis factor and its influence on the performance prediction of wet-cooling towers , 2005 .