Quantitative comparison of FDS and parametric fire curves with post-flashover compartment fire test data

This paper presents a comparison of two parametric fire modelling techniques (Eurocode 1, and the BFD curve method) and one field model (fire dynamics simulator) against large-scale post-flashover test data. Using a method of the product moment correlation coefficient, it is shown that the BFD curve predictions are most closely representative of reality. For the computational test data, two grid resolutions are adopted in the FDS field model, the finer of which having comparable results in terms of regression analysis to the BFD method. Both the field model and the BFD curve method were found to give better predictions compared to the Eurocode method over the duration of the test. However, a direct comparison of the maximum gas temperatures shows the field model to be poorer in its predictive capability than the parametric methods, under-predicting the maximum gas temperatures. In addition, a more in-depth analysis of the FDS predictions indicates that by considering simply average compartment temperatures the more inaccurate spatially specific temperature predictions were disguised. This study provides useful quantitative data on the three techniques presented and discusses more general issues concerning fire modelling.

[1]  Takashi Kashiwagi,et al.  Fire safety science : proceedings of the Fourth international symposium , 1994 .

[2]  Charles Fleischmann,et al.  Experimental Verification Of The Fire Dynamics Simulator Hydrodynamic Model , 2003 .

[3]  J. Hietaniemi,et al.  FDS simulation of fire spread - comparison of model results with experimental data , 2004 .

[4]  Fuchen Jia,et al.  Simulating one of the CIB W14 round robin test cases using the SMARTFIRE fire field model , 2001 .

[5]  Thomas Lennon,et al.  The natural fire safety concept—full-scale tests at Cardington , 2003 .

[6]  Steven J. Emmerich,et al.  Application of a large eddy simulation model to study room airflow , 1998 .

[7]  Weeratunge Malalasekera,et al.  An introduction to computational fluid dynamics - the finite volume method , 2007 .

[8]  Kevin B. McGrattan,et al.  Fire dynamics simulator (ver-sion 3) technical reference guide , 2001 .

[9]  Margaret Law,et al.  Fire grading and fire behaviour , 1991 .

[10]  Ian Burgess,et al.  Analyses of the effects of cooling and fire spread on steel-framed buildings , 1996 .

[11]  Daniel M. Madrzykowski,et al.  Simulation of the Dynamics of the Fire at 3146 Cherry Road NE Washington D.C., May 30, 1999 (NISTIR 6510) , 2000 .

[12]  R. A. Fox,et al.  Introduction to Mathematical Statistics , 1947 .

[13]  Colin Bailey,et al.  Modelling of Compartment Fires: Analysis of the Importance of Grid Resolution and Sub-grid-scale Constants in the Validation of FDS , 2004 .

[14]  C. R. Barnett,et al.  BFD curve: a new empirical model for fire compartment temperatures , 2002 .

[15]  H. Baum,et al.  The Equations of Motion for Thermally Driven, Buoyant Flows. , 1978, Journal of research of the National Bureau of Standards.

[16]  P. Moin,et al.  A dynamic subgrid‐scale eddy viscosity model , 1990 .

[17]  J. Smagorinsky,et al.  GENERAL CIRCULATION EXPERIMENTS WITH THE PRIMITIVE EQUATIONS , 1963 .

[18]  M. Law,et al.  Fire safety of bare external structural steel , 1981 .

[19]  J. Quintiere,et al.  Numerical simulation of axi-symmetric fire plumes: accuracy and limitations , 2003 .