Distribution of long duration current impulses in a test house lightning protection system and electrical equipment

Continuing currents, besides the main short duration return strokes, are ones of the basic components of lightning. Open air experiments were conducted to examine the distribution of continuing current components in lightning protection system, supplying cable and electrical installation of the test house equipped with household appliances. The lightning continuing current was physically simulated using a special current generator of long duration impulses. Current impulses were injected from the generator into air termination of the lightning protection system. Measured current distribution in different parts of the test house were compared with results of previous investigations for short duration lightning current impulses. A small increase of efficiency of the lightning protection system was indicated. It means that the ratio between current flowing along the cable to the grounding system of transformer station (remote ground) and current injected into the local ground was 6-8% less compared with the ratio in case of short duration current impulses representing the lightning return stroke.

[1]  Osmar Pinto,et al.  Waveshapes of continuing currents and properties of M-components in natural negative cloud-to-ground lightning from high-speed video observations , 2007 .

[2]  Vladimir A. Rakov,et al.  Direct lightning strikes to the lightning protective system of a residential building: triggered-lightning experiments , 2002 .

[3]  N. Kitagawa,et al.  Quantitative study of strokes and continuing currents in lightning discharges to ground , 1962 .

[4]  S. Wyderka,et al.  Measurements and modeling of current impulses in the lightning protection system and internal electrical installation equipped with household appliances , 2016 .

[5]  Martin A. Uman,et al.  Continuing current in negative cloud‐to‐ground lightning , 1989 .

[6]  V.A. Rakov,et al.  Distribution of Currents in the Lightning Protective System of a Residential Building—Part I: Triggered-Lightning Experiments , 2008, IEEE Transactions on Power Delivery.

[7]  G. Maslowski,et al.  Testing of Lightning Protective System of a Residential Structure: Comparison of Data Obtained in Rocket-Triggered Lightning and Current Surge Generator Experiments , 2008, 2008 International Conference on High Voltage Engineering and Application.

[8]  V. Rakov,et al.  Lightning: Physics and Effects , 2007 .

[9]  Vladimir A. Rakov,et al.  Current Impulses in the Lightning Protection System of a Test House in Poland , 2015, IEEE Transactions on Electromagnetic Compatibility.

[10]  M. Brook,et al.  Magnetic measurements of thunderstorm currents: 1. Continuing currents in lightning , 1963 .

[11]  Lin Li,et al.  Experimental Investigation and Numerical Modeling of Surge Currents in Lightning Protection System of a Small Residential Structure , 2012 .