A Simple Method for Evaluating Ground-Fault Current Transfer at the Transition Station of a Combined Overhead-Cable Line

When a substation is fed by a combined overhead-cable transmission line, a significant part of the ground fault current flows through cable sheaths and is discharged into the soil at the transition station where cables are connected to the overhead line. Such a phenomenon, known as ldquofault application transfer,rdquo may result in high ground potentials at the transition station which may cause shocks and equipment damage. The scope of this paper is to present new analytic formulas which can be used for the direct calculation of the fault current transferred at the transition station and its ground potential rise as well as the substation earth current. The proposed formulas allow evaluating the influence of the main factors to the fault application transfer phenomenon and can be employed, at the preliminary design stage, to easily assess the most appropriate safety conditions to avoid dangerous effects.

[1]  Ljubivoje Popovic,et al.  REDUCTION FACTOR OF FEEDING LINES THAT HAVE A CABLE AND AN OVERHEAD SECTION , 2003 .

[2]  L. M. Popovic,et al.  Practical method for evaluating ground fault current distribution in station, towers and ground wire , 1998 .

[3]  D. Mukhedkar,et al.  Ground grid design of a transition station system-a typical example of fault transfer , 1990 .

[4]  S. T. Sobral,et al.  Ground potential rise characteristics of urban step-down substations fed by power cables-a practical example , 1988 .

[5]  D. L. Garrett,et al.  Determination of Maximum Substation Grounding System Fault Current Using Graphical Analysis , 1987, IEEE Transactions on Power Delivery.

[6]  L. M. Popovic,et al.  Determination of the reduction factor for feeding cable lines consisting of three single-core cables , 2003 .

[7]  J. Nahman Compact models of nonuniform lines for earthing-system analysis , 2001 .

[8]  L. M. Popovic Practical method for evaluating ground fault current distribution in station supplied by an unhomogeneous line , 1996 .

[9]  D. Mukhedkar,et al.  Ground Fault Current Distribution in Sub-Station, Tower and Ground Wire , 1979, IEEE Transactions on Power Apparatus and Systems.

[10]  A. P. Meliopoulos,et al.  Computation of Maximum Earth Current in Substation Switchyards , 1983, IEEE Power Engineering Review.

[11]  F. Provoost,et al.  Measurement of the current distribution near a substation during a single phase to ground fault , 2003 .

[12]  D. Mukhedkar,et al.  Dimensioning of nearby substations interconnected ground system , 1988 .

[13]  Janos Endrenyi,et al.  Analysis of Transmission Tower Potentials During Ground Faults , 1967 .

[14]  J. M. Nahman,et al.  Grounding Effects of HV and MV Underground Cables Associated with Urban Distribution Substations , 2001, IEEE Power Engineering Review.