Study of the Smoke Control Characteristics for Fire Near Jet Fans

In this research, we conducted a PIV-visualization experiment to smoke control from fires by using a neighboring Jet fan at minimum distance. We also compared our experiment results with FDS numerical analysis ones. As a result of quantitative data analysis of smoke control modes against fires in tunnel, we concluded that a neighboring Jet fan should be placed at least 25 m away from its fire source in order to produce satisfactory smoke control results. Jet fan showed the best smoke-controlling performance, if placed 50 m away from its fire source. It tended to show an overspeed around the center of tunnel when it is placed more than 75 away from its fire source.